防火卷簾門安裝規范
1、安裝卷簾門的洞口上部不得設有通風管(guan)、水管(guan)等;
2、電源(yuan)線(xian)路(三相五線(xian)和消(xiao)防中控(kong)信號線(xian))由用戶鋪(pu)設(she)到卷門機旁(pang)的電氣(qi)控(kong)制箱邊;
3、卷簾門安裝好后,安裝吊頂(ding),吊頂(ding)邊(bian)緣應離(li)簾板50MM,以免磨擦(ca);
4、調(diao)試及使用時,嚴禁底部站人。電器設施不得擅自拆(chai)搬(ban);
5、根(gen)據消(xiao)防(fang)管(guan)理規定(ding),防(fang)火卷簾門為消(xiao)防(fang)專用(yong)設施,不得(de)改作他用(yong),卷簾正(zheng)下方不得(de)堆放任何物品;
6、安(an)裝調(diao)試后(hou),每季度啟(qi)動(dong)一次,以檢查(cha)電器(qi)、機械(xie)性能(neng),檢查(cha)時注意操作安(an)全。
防火簾卷門安裝注意事項
1、防火卷簾門電源
防(fang)火卷簾(lian)門的供電(dian)(dian)電(dian)(dian)源應為(wei)消防(fang)電(dian)(dian)源;供電(dian)(dian)和(he)控制導線截面積、絕緣(yuan)電(dian)(dian)阻、線路(lu)敷設(she)和(he)保護管材質應符(fu)合(he)規范(fan)要求。防(fang)火卷簾(lian)門供電(dian)(dian)裝置的過電(dian)(dian)流保護整定值應符(fu)合(he)設(she)計(ji)要求。
2、防火卷簾門控制器
防(fang)火(huo)卷(juan)簾門(men)上面安裝有防(fang)火(huo)卷(juan)簾門(men)控(kong)(kong)制器控(kong)(kong)制防(fang)火(huo)卷(juan)簾門(men)進行上、下(xia)、停(ting)等動(dong)作。還要在兩側(人員無法操作側除外(wai))分別設置手動(dong)按鈕(niu)控(kong)(kong)制電動(dong)防(fang)火(huo)卷(juan)簾門(men)的(de)升(sheng)、降、停(ting),并應在防(fang)火(huo)卷(juan)簾門(men)火(huo)災(zai)時下(xia)降關閉后提升(sheng)該防(fang)火(huo)卷(juan)簾門(men)的(de)功(gong)能,且(qie)該防(fang)火(huo)卷(juan)簾門(men)提升(sheng)到(dao)位后應能自動(dong)恢(hui)復原關閉狀(zhuang)態。
3、防火卷簾門的報警系統
防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)應(ying)(ying)該設有(you)自(zi)(zi)動(dong)(dong)報警控(kong)制(zhi)系統的電動(dong)(dong)防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)應(ying)(ying)設有(you)自(zi)(zi)動(dong)(dong)關閉(bi)控(kong)制(zhi)裝置(zhi),用于疏散通道上(shang)的防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)應(ying)(ying)有(you)由探測(ce)器(qi)控(kong)制(zhi)兩步下(xia)(xia)降(jiang)或下(xia)(xia)降(jiang)到1.5m~1.8m后延時下(xia)(xia)降(jiang)到底功能(neng);用于只(zhi)起(qi)到防(fang)火(huo)(huo)分隔作用的卷(juan)(juan)(juan)簾(lian)(lian)(lian)應(ying)(ying)一步下(xia)(xia)降(jiang)到底,手(shou)動(dong)(dong)速放(fang)裝置(zhi),防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)手(shou)動(dong)(dong)速放(fang)裝置(zhi)的臂力不大(da)于50N;消(xiao)防(fang)控(kong)制(zhi)室應(ying)(ying)有(you)強制(zhi)電動(dong)(dong)防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)下(xia)(xia)降(jiang)功能(neng)(應(ying)(ying)急操作裝置(zhi))并顯示其狀態;安裝在疏散通道上(shang)的防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)的啟(qi)閉(bi)裝置(zhi)應(ying)(ying)能(neng)在火(huo)(huo)災斷電后手(shou)動(dong)(dong)機械提升以下(xia)(xia)降(jiang)關閉(bi)的防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men),并且該防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)能(neng)依靠其自(zi)(zi)重重新恢復原關閉(bi)狀態。手(shou)動(dong)(dong)防(fang)火(huo)(huo)卷(juan)(juan)(juan)簾(lian)(lian)(lian)門(men)(men)手(shou)動(dong)(dong)下(xia)(xia)放(fang)牽引力不大(da)于150N。
在防火卷簾(lian)(lian)門(men)安(an)裝完之后一定要檢查一下(xia)以上的幾點設(she)備及注(zhu)意下(xia)事(shi)項(xiang),把消防中控的信(xin)號(hao)線連接(jie)到(dao)防火卷簾(lian)(lian)門(men)控制器上就完全的整個防火卷簾(lian)(lian)門(men)消防聯動的功能。