防火卷簾門安裝規范
1、安裝卷(juan)簾門的洞(dong)口(kou)上部不得設有通風(feng)管(guan)(guan)、水管(guan)(guan)等(deng);
2、電源線路(三相五線和(he)消防中控(kong)信(xin)號(hao)線)由(you)用戶鋪設到卷門(men)機旁的電氣控(kong)制箱邊;
3、卷簾門安裝好后,安裝吊頂(ding)(ding),吊頂(ding)(ding)邊緣應離簾板50MM,以免磨擦;
4、調(diao)試(shi)及使用時,嚴禁(jin)底部站(zhan)人(ren)。電器(qi)設(she)施不得(de)擅自拆(chai)搬;
5、根據消防管理規定(ding),防火(huo)卷簾門(men)為消防專(zhuan)用設施,不得改(gai)作他用,卷簾正下方不得堆放任(ren)何物品;
6、安裝調試后,每季度啟動一(yi)次,以(yi)檢查電器、機械性能,檢查時注意操作安全。
防火簾卷門安裝注意事項
1、防火卷簾門電源
防(fang)火卷(juan)簾門的供(gong)(gong)電(dian)電(dian)源應(ying)(ying)為消防(fang)電(dian)源;供(gong)(gong)電(dian)和(he)控(kong)制(zhi)導線截面積(ji)、絕緣電(dian)阻(zu)、線路敷(fu)設和(he)保(bao)護管材質(zhi)應(ying)(ying)符合(he)規范要(yao)求。防(fang)火卷(juan)簾門供(gong)(gong)電(dian)裝置的過電(dian)流保(bao)護整定值(zhi)應(ying)(ying)符合(he)設計要(yao)求。
2、防火卷簾門控制器
防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門上(shang)面(mian)安裝有防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門控制(zhi)器控制(zhi)防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門進行上(shang)、下、停等動(dong)(dong)作。還要在兩側(人員(yuan)無法操(cao)作側除外)分(fen)別設置手(shou)動(dong)(dong)按鈕控制(zhi)電(dian)動(dong)(dong)防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門的升(sheng)、降(jiang)(jiang)、停,并應在防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門火(huo)(huo)(huo)(huo)災時下降(jiang)(jiang)關(guan)閉(bi)后提升(sheng)該防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門的功(gong)能(neng),且該防(fang)(fang)火(huo)(huo)(huo)(huo)卷(juan)(juan)簾門提升(sheng)到位后應能(neng)自動(dong)(dong)恢復原關(guan)閉(bi)狀態。
3、防火卷簾門的報警系統
防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)應(ying)(ying)該設有(you)(you)自(zi)動(dong)(dong)(dong)報警(jing)控制系統的(de)(de)電(dian)動(dong)(dong)(dong)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)應(ying)(ying)設有(you)(you)自(zi)動(dong)(dong)(dong)關閉(bi)(bi)控制裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi),用于疏散通道(dao)上(shang)(shang)的(de)(de)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)應(ying)(ying)有(you)(you)由探測器(qi)控制兩步(bu)下(xia)(xia)降(jiang)或下(xia)(xia)降(jiang)到(dao)1.5m~1.8m后延時下(xia)(xia)降(jiang)到(dao)底功(gong)能(neng)(neng);用于只起到(dao)防火(huo)分隔作(zuo)用的(de)(de)卷(juan)(juan)(juan)簾(lian)應(ying)(ying)一(yi)步(bu)下(xia)(xia)降(jiang)到(dao)底,手(shou)動(dong)(dong)(dong)速放(fang)裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi),防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)手(shou)動(dong)(dong)(dong)速放(fang)裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)的(de)(de)臂(bei)力不大(da)于50N;消(xiao)防控制室應(ying)(ying)有(you)(you)強(qiang)制電(dian)動(dong)(dong)(dong)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)下(xia)(xia)降(jiang)功(gong)能(neng)(neng)(應(ying)(ying)急操作(zuo)裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi))并顯(xian)示(shi)其(qi)狀態(tai);安裝(zhuang)(zhuang)(zhuang)在疏散通道(dao)上(shang)(shang)的(de)(de)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)的(de)(de)啟(qi)閉(bi)(bi)裝(zhuang)(zhuang)(zhuang)置(zhi)(zhi)應(ying)(ying)能(neng)(neng)在火(huo)災(zai)斷電(dian)后手(shou)動(dong)(dong)(dong)機械(xie)提(ti)升以下(xia)(xia)降(jiang)關閉(bi)(bi)的(de)(de)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men),并且該防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)能(neng)(neng)依靠其(qi)自(zi)重重新恢復原(yuan)關閉(bi)(bi)狀態(tai)。手(shou)動(dong)(dong)(dong)防火(huo)卷(juan)(juan)(juan)簾(lian)門(men)(men)(men)(men)手(shou)動(dong)(dong)(dong)下(xia)(xia)放(fang)牽引(yin)力不大(da)于150N。
在防(fang)火(huo)卷(juan)簾門(men)(men)安裝完之后一(yi)定要檢查一(yi)下以上的幾點設備(bei)及注意下事項,把消防(fang)中(zhong)控的信號線連(lian)接到防(fang)火(huo)卷(juan)簾門(men)(men)控制器上就(jiu)完全的整個防(fang)火(huo)卷(juan)簾門(men)(men)消防(fang)聯動的功能。
申明:以上內容源于程序系統索引或網民分享提供,僅供您參考使用,不代表本網站的研究觀點,請注意甄別內容來源的真實性和權威性。