一、消火栓按鈕能直接啟動水泵嗎
能(neng)。GB50116-2013《火(huo)災自動(dong)(dong)報警系統設計(ji)規范》(2014年5月(yue)1日實(shi)施)4.3消火(huo)栓(shuan)系統的(de)聯(lian)動(dong)(dong)控(kong)(kong)制設計(ji)中(zhong)有明確表述:當設置消火(huo)栓(shuan)按(an)鈕時,消火(huo)栓(shuan)按(an)鈕的(de)動(dong)(dong)作信號(hao)(hao)應作為報警信號(hao)(hao)及啟(qi)動(dong)(dong)消火(huo)栓(shuan)泵的(de)聯(lian)動(dong)(dong)觸發信號(hao)(hao),由消防聯(lian)動(dong)(dong)控(kong)(kong)制器(qi)聯(lian)動(dong)(dong)控(kong)(kong)制消火(huo)栓(shuan)泵的(de)啟(qi)動(dong)(dong)。
當(dang)建筑物內設有火災(zai)自(zi)動(dong)(dong)報警(jing)系(xi)統(tong)(tong)時,消(xiao)(xiao)火栓(shuan)按鈕的動(dong)(dong)作信(xin)號(hao)作為火災(zai)報警(jing)系(xi)統(tong)(tong)和消(xiao)(xiao)火栓(shuan)系(xi)統(tong)(tong)的聯動(dong)(dong)觸發信(xin)號(hao),由消(xiao)(xiao)防(fang)聯動(dong)(dong)控制器(qi)(qi)聯動(dong)(dong)控制消(xiao)(xiao)防(fang)泵(beng)啟動(dong)(dong),消(xiao)(xiao)防(fang)泵(beng)的動(dong)(dong)作信(xin)號(hao)作為系(xi)統(tong)(tong)的聯動(dong)(dong)反(fan)饋(kui)信(xin)號(hao)應(ying)反(fan)饋(kui)至(zhi)消(xiao)(xiao)防(fang)控制室,并在消(xiao)(xiao)防(fang)聯動(dong)(dong)控制器(qi)(qi)上顯(xian)示(shi)。消(xiao)(xiao)火栓(shuan)按鈕經聯動(dong)(dong)控制器(qi)(qi)啟動(dong)(dong)消(xiao)(xiao)防(fang)泵(beng)的優點是減(jian)少(shao)布線量和線纜(lan)使用量,提高(gao)整個消(xiao)(xiao)火栓(shuan)系(xi)統(tong)(tong)的可靠性。
二、消火栓按鈕和手動報警按鈕區別
1、功能區別
手動(dong)報(bao)警(jing)按鈕是火(huo)災(zai)自(zi)動(dong)報(bao)警(jing)系統的(de)手動(dong)觸發(fa)裝置,簡單(dan)的(de)說就是供人(ren)員現(xian)場發(fa)現(xian)火(huo)災(zai)時(shi),人(ren)工手動(dong)按下按鈕向消防主(zhu)機反(fan)饋(kui)火(huo)災(zai)報(bao)警(jing)信(xin)號。
而消火栓按鈕,俗稱“破(po)玻按鈕”,消火栓按鈕作用主要是在發生火災人員使(shi)用室內消火栓滅火時(shi),按下按鈕啟動消火栓泵加壓,同時(shi)向消防主機反饋使(shi)用消火栓的位(wei)置信息。
2、設置原理區別
設置手動報警(jing)按(an)鈕的目的是報警(jing),消防控制(zhi)中心主機或區域(yu)火災報警(jing)控制(zhi)器接到(dao)報警(jing)后,需(xu)經確認,排除誤報后,方可發(fa)出(chu)聯動控制(zhi)信號,其(qi)性(xing)質等同于探測器報警(jing),其(qi)管線(xian)為報警(jing)線(xian)路,沒有耐火要求(qiu)。
設置消(xiao)火栓按鈕的(de)目的(de)是為了(le)啟動消(xiao)防(fang)泵,直接送(song)至(zhi)消(xiao)防(fang)泵控制柜,并不需要經過消(xiao)防(fang)中(zhong)心(xin)確認,其(qi)管線屬于(yu)控制線路,有耐火要求。
3、設置規范要求區別
手(shou)(shou)(shou)動(dong)報(bao)警(jing)按鈕(niu)(niu):每(mei)個防(fang)火(huo)(huo)(huo)分(fen)(fen)區應至少設(she)置(zhi)(zhi)(zhi)一(yi)只手(shou)(shou)(shou)動(dong)火(huo)(huo)(huo)災(zai)報(bao)警(jing)按鈕(niu)(niu);從(cong)一(yi)個防(fang)火(huo)(huo)(huo)分(fen)(fen)區內的(de)任何位置(zhi)(zhi)(zhi)到最(zui)鄰近的(de)手(shou)(shou)(shou)動(dong)火(huo)(huo)(huo)災(zai)報(bao)警(jing)按鈕(niu)(niu)的(de)步行距離(li)不應大于(yu)30m(當不能滿(man)足該要求則需要增(zeng)加按鈕(niu)(niu)數量)。手(shou)(shou)(shou)動(dong)火(huo)(huo)(huo)災(zai)報(bao)警(jing)按鈕(niu)(niu)宜設(she)置(zhi)(zhi)(zhi)在疏散通道或出入(ru)口處。列車(che)上(shang)設(she)置(zhi)(zhi)(zhi)的(de)手(shou)(shou)(shou)動(dong)火(huo)(huo)(huo)災(zai)報(bao)警(jing)按鈕(niu)(niu),應設(she)置(zhi)(zhi)(zhi)在每(mei)節車(che)廂的(de)出入(ru)口和中間部位。
手動火災報警按鈕(niu)應(ying)設置(zhi)在明顯和便于操作的(de)部位。當采用(yong)壁掛方(fang)式安(an)裝(zhuang)時(shi),其底邊距地高(gao)度宜(yi)為1.3m~1.5m,且應(ying)有明顯的(de)標志。
消(xiao)火(huo)(huo)栓(shuan)(shuan)(shuan)按鈕(niu):當設(she)置消(xiao)火(huo)(huo)栓(shuan)(shuan)(shuan)按鈕(niu)時,消(xiao)火(huo)(huo)栓(shuan)(shuan)(shuan)按鈕(niu)的動(dong)作信號應作為報警信號及啟動(dong)消(xiao)火(huo)(huo)栓(shuan)(shuan)(shuan)泵的聯動(dong)觸發(fa)信號,由消(xiao)防(fang)聯動(dong)控制器聯動(dong)控制消(xiao)火(huo)(huo)栓(shuan)(shuan)(shuan)泵的啟動(dong)。
縱觀現行(xing)相(xiang)關(guan)規(gui)范,未能找到有關(guan)要求設(she)置(zhi)消火(huo)(huo)栓(shuan)按(an)鈕的(de)規(gui)定(ding),但目前的(de)消防設(she)計中,只要建筑(zhu)設(she)置(zhi)了(le)火(huo)(huo)災自動報(bao)警系統和(he)室內(nei)(nei)消火(huo)(huo)栓(shuan)系統,一(yi)般都設(she)置(zhi)消火(huo)(huo)栓(shuan)按(an)鈕,而且每個室內(nei)(nei)消火(huo)(huo)栓(shuan)處均對應一(yi)個消火(huo)(huo)栓(shuan)按(an)鈕。
消火栓按(an)鈕(niu)和手動(dong)報(bao)警按(an)鈕(niu)從設置(zhi)原理和功能(neng)上說不能(neng)相互(hu)代替。從實(shi)際使用(yong)方法(fa)和效果上看(kan)兩者的區別較為(wei)模糊(hu),特(te)別是如果消火(huo)栓按(an)鈕(niu)啟泵信號先送至(zhi)消防中心,然后(hou)再(zai)(zai)從消防中心再(zai)(zai)接至(zhi)消防泵控制柜,也一(yi)直存(cun)在不同(tong)看(kan)法(fa)。
由于火災(zai)自動(dong)報(bao)警系統(tong)設(she)計規范中并未明確規定必須(xu)設(she)置消火栓按(an)鈕,因此有些(xie)工程(cheng)在只在消火栓旁邊設(she)置手動(dong)報(bao)警按(an)鈕,同時兼消火栓按(an)鈕的功能,消火栓內未設(she)消火栓按(an)鈕,這種做法也(ye)通過了(le)消防部門的驗收。