一、防爆壓力變送器規格參數有哪些
1、精度等級:0.25級(ji)基本誤(wu)差±0.25%、0.5級(ji)基本誤(wu)差±0.5%
2、非線性誤差:0.25級(ji)≤±0.25%FS、0.5級(ji)≤±0.5%FS
3、輸出特性:兩線(xian)制4-20mA輸出(chu)的品種,標準供(gong)(gong)電(dian)(dian)(dian)(dian)DC24V,負(fu)載電(dian)(dian)(dian)(dian)阻(zu)大于600Ω時,每增加50Ω需增加1V供(gong)(gong)電(dian)(dian)(dian)(dian),但供(gong)(gong)電(dian)(dian)(dian)(dian)極限為(wei)DC45V,當需要超(chao)過(guo)DC24V供(gong)(gong)電(dian)(dian)(dian)(dian)時,輸出(chu)回路應(ying)避免(mian)長期工作在零(ling)(ling)負(fu)載電(dian)(dian)(dian)(dian)阻(zu)狀(zhuang)態(tai),必要時可在輸出(chu)回路中串(chuan)入(ru)電(dian)(dian)(dian)(dian)阻(zu)以降低輸出(chu)功率管的功耗,零(ling)(ling)負(fu)載電(dian)(dian)(dian)(dian)阻(zu)時供(gong)(gong)電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)壓DC12V
4、模擬量:二線制4~20mADC
5、數字量:兩線制(zhi)4~20mADC并(bing)疊加符合HART協議的過程變量數字信號
6、電源:供電電壓(ya)12.5~45VDC
7、負載限制:回(hui)路***負載電(dian)阻(zu)Rmax取決(jue)于供電(dian)電(dian)壓。HART通訊要求負載電(dian)阻(zu)不低于250Ω,不高于600Ω。
7、通訊距離:RS485通訊距離(li)為1.5Km,多站通訊最多可接15臺智能變送(song)器
8、輸出顯示:四位制數字顯示、五(wu)位LCD液晶顯示、指(zhi)針式
9、防爆形式:本安型:ExiaII CT5,隔爆(bao)型
10、零點遷移范圍:零點可隨(sui)意正遷移或負遷移,但不得使(shi)設定的測量范圍上下限(xian)和量程超出極(ji)限(xian)值(zhi)。
11、溫度范圍:環(huan)境(jing)溫(wen)度:-40~85℃(選用LCD指示表(biao)時為-20~70℃)
12、測量介質溫度:-40~104℃
13、靜壓和單向超壓范圍:3.45Kpa(絕壓)~31.2MPa(表(biao)壓)
14、相對濕度:5~98%RH
15、啟動時間:5秒內啟動
16、容量變化量:小于0.16cm3
17、阻尼調整:時間常熟0.20~25秒
18、故障報警:如(ru)傳感器或電路(lu)出現故障,自動診斷功(gong)能將(jiang)自動輸出3.9或21.0mA
19、組態保護:為了避免變送(song)器的組態數(shu)據(ju)(ju)被(bei)隨意改動(dong),可通過軟件或保護開關鎖定(ding)存儲的數(shu)據(ju)(ju)
二、防爆壓力變送器外殼是否需要接地
在《石油化工儀表工程施工技術規程》、《石油化工儀表接地設計規范》、《儀表系統接地設計規范》《自動化儀表工程施工及質量驗收規范》等規范中得出結論:防爆壓力變送器外(wai)殼是需要接地的。
1、供電(dian)電(dian)壓高于(yu)36V或有可能帶有危險電(dian)壓的現場儀(yi)表金屬裸露(lu)部(bu)分正(zheng)常不帶電(dian)的,均(jun)做保護接(jie)地。
2、供電電壓不(bu)高(gao)于36V的(de)現場儀表金屬(shu)裸露(lu)部分(fen),無(wu)特殊要求時,可不(bu)做保(bao)護接地。
3、非防爆危(wei)險區域(yu)的(de)金屬盤、板上安裝的(de)按鈕、信(xin)號(hao)燈、繼(ji)電(dian)器(qi)等(deng)小型低壓電(dian)器(qi)的(de)金屬盤、板已良好接地,可(ke)不做保護接地。
4、爆(bao)炸(zha)性危險環境(jing)的電氣設(she)備、電纜保護管(guan)、接線箱等(deng)金屬裸露部分,均應接地。