一、防爆壓力變送器規格參數有哪些
1、精度等級:0.25級基(ji)本誤(wu)差±0.25%、0.5級基(ji)本誤(wu)差±0.5%
2、非線性誤差:0.25級(ji)≤±0.25%FS、0.5級(ji)≤±0.5%FS
3、輸出特性:兩線制(zhi)4-20mA輸(shu)出的(de)品(pin)種,標準供電(dian)(dian)(dian)DC24V,負(fu)載電(dian)(dian)(dian)阻大(da)于600Ω時,每增加50Ω需增加1V供電(dian)(dian)(dian),但供電(dian)(dian)(dian)極限為DC45V,當(dang)需要超過DC24V供電(dian)(dian)(dian)時,輸(shu)出回路應避免長期工作在零(ling)負(fu)載電(dian)(dian)(dian)阻狀態,必要時可在輸(shu)出回路中串入電(dian)(dian)(dian)阻以降(jiang)低輸(shu)出功(gong)率(lv)管(guan)的(de)功(gong)耗,零(ling)負(fu)載電(dian)(dian)(dian)阻時供電(dian)(dian)(dian)電(dian)(dian)(dian)壓DC12V
4、模擬量:二線制4~20mADC
5、數字量:兩線制4~20mADC并疊加符合HART協議的過(guo)程(cheng)變(bian)量數字信(xin)號
6、電源:供電(dian)電(dian)壓12.5~45VDC
7、負載限制:回(hui)路(lu)***負(fu)載電阻Rmax取決于(yu)供電電壓。HART通訊(xun)要求負(fu)載電阻不(bu)低于(yu)250Ω,不(bu)高于(yu)600Ω。
7、通訊距離:RS485通訊距離為1.5Km,多(duo)站通訊最多(duo)可接15臺(tai)智能變送器
8、輸出顯示:四位制(zhi)數字(zi)顯示(shi)、五位LCD液晶顯示(shi)、指針式
9、防爆形式:本安型(xing):ExiaII CT5,隔爆型(xing)
10、零點遷移范圍:零點可隨(sui)意正(zheng)遷移或負遷移,但不得使設定的測量范圍上下(xia)限(xian)和量程超出(chu)極限(xian)值。
11、溫度范圍:環(huan)境溫度:-40~85℃(選用LCD指(zhi)示表時為-20~70℃)
12、測量介質溫度:-40~104℃
13、靜壓和單向超壓范圍:3.45Kpa(絕壓)~31.2MPa(表壓)
14、相對濕度:5~98%RH
15、啟動時間:5秒內啟動
16、容量變化量:小于0.16cm3
17、阻尼調整:時(shi)間常熟0.20~25秒
18、故障報警:如(ru)傳感器(qi)或電(dian)路(lu)出(chu)(chu)現故障,自(zi)動(dong)診(zhen)斷功能將自(zi)動(dong)輸(shu)出(chu)(chu)3.9或21.0mA
19、組態保護:為了避(bi)免(mian)變(bian)送器的組態數(shu)據被隨意(yi)改動(dong),可通過軟件或保(bao)護開關鎖定存儲的數(shu)據
二、防爆壓力變送器外殼是否需要接地
在《石油化工儀表工程施工技術規程》、《石油化工儀表接地設計規范》、《儀表系統接地設計規范》《自動化儀表工程施工及質量驗收規范》等規范中得出結論:防爆壓力變送器外殼(ke)是需要接地(di)的。
1、供電電壓高于36V或(huo)有可能帶有危(wei)險電壓的現場(chang)儀(yi)表金屬(shu)裸露部分正(zheng)常(chang)不(bu)帶電的,均做(zuo)保護接地。
2、供電電壓不高于36V的現場儀表金(jin)屬裸露部分,無(wu)特殊要求(qiu)時,可不做保(bao)護接地。
3、非防(fang)爆危險區域(yu)的(de)金(jin)(jin)屬盤、板上安裝的(de)按(an)鈕、信號燈、繼電器等小型低壓電器的(de)金(jin)(jin)屬盤、板已(yi)良好接(jie)地,可不做保護(hu)接(jie)地。
4、爆炸性危險環境的電氣設備(bei)、電纜保護管、接(jie)線箱等(deng)金屬(shu)裸露(lu)部分,均應接(jie)地。