一、三相多功能電力儀表校驗方法
多功能(neng)電力儀表應定期進行校(xiao)(xiao)驗(yan),保證測量的(de)準確性,具體的(de)校(xiao)(xiao)驗(yan)方法(fa)步驟如下:
1、校驗前
(1)查看多功能電力儀表是否接入儀表電(dian)源,有無(wu)示(shi)數(shu)。若無(wu)示(shi)數(shu)顯示(shi),則檢查(cha)電(dian)源線,控制電(dian)源回路。
(2)外觀檢查(cha),檢查(cha)是否(fou)有缺角,看是否(fou)有零件(jian)脫(tuo)落(luo)或損壞之處,緊固件(jian)是否(fou)松動,電路連接線是否(fou)開焊等顯(xian)示(shi)不(bu)正常(chang)情況。
(3)記錄下(xia)該多(duo)功能(neng)電力儀表(biao)的銘(ming)牌,包括(kuo)生(sheng)產日(ri)期、廠家、精度(du)、出廠日(ri)期、編號、變比(bi)、型(xing)號、天(tian)氣情況、環境溫度(du)、環境濕度(du)等。二(er)次回(hui)路清(qing)掃(sao)檢(jian)查,電流表(biao)CT,電壓表(biao)PT,功率表(biao)PT/CT二(er)次側回(hui)路清(qing)掃(sao),檢(jian)查。
2、主要參數校驗過程
(1)原理
次(ci)級線圈的(de)額(e)定電(dian)(dian)壓(ya)(ya)(ya)一般設(she)(she)計(ji)為(wei)100V,與(yu)其(qi)(qi)配套使用的(de)交流(liu)電(dian)(dian)壓(ya)(ya)(ya)表量程也(ye)應(ying)(ying)為(wei)100V,通(tong)過變(bian)比(bi)換算出(chu)一次(ci)側線電(dian)(dian)壓(ya)(ya)(ya)的(de)標準值。次(ci)級線圈的(de)額(e)定電(dian)(dian)流(liu)一般設(she)(she)計(ji)為(wei)5A,與(yu)其(qi)(qi)配套使用的(de)交流(liu)電(dian)(dian)流(liu)表量程也(ye)應(ying)(ying)為(wei)5A,通(tong)過變(bian)比(bi)換算出(chu)一次(ci)側相(xiang)電(dian)(dian)流(liu)的(de)標準值,然后根據電(dian)(dian)流(liu)電(dian)(dian)壓(ya)(ya)(ya),換算出(chu)有功(gong)(gong)(gong)功(gong)(gong)(gong)率,無功(gong)(gong)(gong)功(gong)(gong)(gong)率等。
(2)電壓校驗
按照(zhao)多功(gong)能電力(li)儀(yi)(yi)(yi)表說明書正確(que)設置儀(yi)(yi)(yi)表參(can)數,在校驗裝置上(shang)輸(shu)入”11.547U”然后按“Enter”鍵,則(ze)此時裝置對(dui)多功(gong)能電力(li)儀(yi)(yi)(yi)表ABC三相(xiang)輸(shu)入11.547V相(xiang)電壓,二次線(xian)電壓為(wei)20V。操作多功(gong)能電力(li)儀(yi)(yi)(yi)表到(dao)電壓顯(xian)示界面,記錄下(xia)多功(gong)能電力(li)儀(yi)(yi)(yi)表線(xian)電壓顯(xian)示數據(ju)。然后按照(zhao)上(shang)述(shu)方法(fa)分別,在檢測裝置輸(shu)入23.094U,34.642U,46.189U,57.737U,記錄多功(gong)能電力(li)儀(yi)(yi)(yi)表線(xian)電壓顯(xian)示數據(ju)。
(3)電流校驗
檢測(ce)裝置上先按(an)(an)Menu鍵進(jin)入主(zhu)菜單,然(ran)后按(an)(an)“1交流輸(shu)(shu)出“進(jin)入交流輸(shu)(shu)出界面,按(an)(an)V/Y鍵,用于Y型或V型接線方式(shi)選擇(ze),一(yi)般多(duo)(duo)數(shu)為(wei)Y型接法(fa),按(an)(an)IRange量(liang)程(cheng)鍵選擇(ze)合適量(liang)程(cheng),一(yi)般電(dian)流互感器二次側電(dian)流為(wei)5A。輸(shu)(shu)入”1I”然(ran)后按(an)(an)Enter鍵,則此時(shi)裝置對儀(yi)表(biao)ABC三(san)相輸(shu)(shu)入1安培電(dian)流,調(diao)節多(duo)(duo)功能電(dian)力儀(yi)表(biao)到電(dian)流顯(xian)示界面,記(ji)錄(lu)下多(duo)(duo)功能電(dian)力儀(yi)表(biao)顯(xian)示數(shu)據。然(ran)后按(an)(an)照(zhao)上述方法(fa),分別輸(shu)(shu)入2I,3I,4I,5I,記(ji)錄(lu)下多(duo)(duo)功能電(dian)力儀(yi)表(biao)顯(xian)示數(shu)據。
(4)有功功率,無功功率,功率因素校驗
A、有(you)(you)功(gong)(gong)功(gong)(gong)率(lv):在檢(jian)測裝置上選擇好(hao)電(dian)(dian)(dian)壓(ya)電(dian)(dian)(dian)流(liu)相對應的量程和接(jie)線(xian)方式,輸(shu)入57.737U然(ran)后(hou)按Enter鍵。按快捷(jie)鍵區(qu)“Φ試驗(yan)點1.0”,調(diao)整儀表功(gong)(gong)率(lv)為(wei)有(you)(you)功(gong)(gong)功(gong)(gong)率(lv)模式,輸(shu)入”1I”然(ran)后(hou)按Enter鍵,則此時裝置對多功(gong)(gong)能電(dian)(dian)(dian)力儀表ABC三相輸(shu)入1安培電(dian)(dian)(dian)流(liu),線(xian)電(dian)(dian)(dian)壓(ya)100V。調(diao)節多功(gong)(gong)能電(dian)(dian)(dian)力儀表到有(you)(you)功(gong)(gong)功(gong)(gong)率(lv)顯示(shi)界面(mian),記(ji)錄下(xia)數(shu)據。然(ran)后(hou)按照上述方法,分別(bie)輸(shu)入2I,3I,4I,5I,記(ji)錄下(xia)數(shu)據。
B、無功(gong)功(gong)率:在檢測裝置上按快(kuai)捷(jie)鍵區“Φ試(shi)(shi)驗點(dian)0.0L”或“Φ試(shi)(shi)驗點(dian)0.0C”調整(zheng)多功(gong)能電力(li)(li)儀(yi)表功(gong)率為無功(gong)功(gong)率模式,然后在分(fen)別輸入1I、2I、3I、4I、5I,調節多功(gong)能電力(li)(li)儀(yi)表到無功(gong)功(gong)功(gong)率顯示界(jie)面(mian),記錄下數據。
C、功率因(yin)素(su):在(zai)檢測裝置(zhi)上分別(bie)按快捷鍵區“Φ試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)0.0L”、“Φ試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)0.5L”、“試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)1.0”、“Φ試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)0.8C”、“Φ試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)0.5C”、“Φ試(shi)(shi)驗(yan)(yan)點(dian)(dian)(dian)0.0C”,調節多功能(neng)電力儀(yi)表到功率因(yin)素(su)顯示界面,記錄下數據(ju)。
3、校驗后
(1)對電源控制回(hui)路(lu)經(jing)行檢(jian)查,由于實驗所(suo)斷開的控制開關,拔掉的熔絲,都要經(jing)行復歸。
(2)對于(yu)直(zhi)接加線(xian)(xian)到多功能電力(li)儀(yi)表上(shang)的實(shi)驗,實(shi)驗后要注意復歸過功能電力(li)儀(yi)表上(shang)的原來所脫開(kai)的導線(xian)(xian),保證接線(xian)(xian)正確(que)。
(3)對于端子(zi)排上電壓,電流回路進行檢查,由于實驗所拆的滑片(pian),導線(xian)都要(yao)經行復歸。
二、多功能電力儀表校驗常見問題及處理方法
多功能電力儀表校(xiao)驗過程中(zhong),可能會遇到一些(xie)問題,下面為大家(jia)介紹一下這些(xie)問題的處理(li)方(fang)法(fa):
1、為了(le)檢測儀(yi)表(biao)回(hui)路(lu),一(yi)般情況(kuang)下先從(cong)端子(zi)排上進行實驗。因此要(yao)注意(yi)通過變壓器二次(ci)(ci)(ci)側(ce)向一(yi)次(ci)(ci)(ci)側(ce)反向送電,必須先把相對應的電壓二次(ci)(ci)(ci)側(ce)回(hui)路(lu)斷開(kai)。一(yi)般也要(yao)在(zai)端子(zi)排上把電流互感器二次(ci)(ci)(ci)測的回(hui)路(lu)滑(hua)片脫(tuo)開(kai)。
2、進行(xing)電(dian)(dian)(dian)壓(ya)校驗時,注意(yi)電(dian)(dian)(dian)壓(ya)回路是否(fou)有電(dian)(dian)(dian)器元件導致(zhi)所加的(de)電(dian)(dian)(dian)壓(ya)分壓(ya),造成數據的(de)誤差。
3、若端子(zi)排(pai)線路復雜,無(wu)法進行試驗,則(ze)可以直(zhi)接把電(dian)(dian)壓(ya),電(dian)(dian)流加(jia)在(zai)儀(yi)表上,應(ying)注(zhu)意要脫開(kai)外電(dian)(dian)路,所(suo)加(jia)電(dian)(dian)壓(ya)線的(de)觸頭應(ying)該保(bao)持一(yi)定間(jian)隙,防止短路。
4、若發現所(suo)測電(dian)壓,電(dian)流數據有微小波(bo)動時,因先(xian)檢(jian)查(cha)是否所(suo)加頻(pin)率(lv)是50Hz,然后先(xian)把電(dian)壓,電(dian)流加到(dao)滿(man)量程,一般情況下可(ke)以消除波(bo)動。
5、若發現(xian)所(suo)測的電壓,電流,有功(gong),無功(gong)的值與(yu)標準值有明顯差(cha)異時,因先(xian)檢查是(shi)否(fou)是(shi)回路問題,加錯線或者相(xiang)序弄等,然后在檢查是(shi)否(fou)是(shi)該表變比(bi)問題,與(yu)之前所(suo)記錄的電壓互感(gan)器(qi)、電流互感(gan)器(qi)變比(bi),進(jin)行比(bi)較。若設(she)置錯誤,則對(dui)多功(gong)能電力儀表進(jin)行設(she)置,設(she)置正(zheng)確后,在進(jin)行校驗。
6、若發現所測(ce)電(dian)流(liu)表,功(gong)率表是顯示負數,則要(yao)檢(jian)查是否是所加電(dian)流(liu)極性錯誤。