1、定期巡(xun)視檢測(ce)通(tong)信(xin)電(dian)源設(she)備。注意(yi)機(ji)房環(huan)境(jing)溫度(du)和(he)設(she)備運行(xing)狀況,利用通(tong)信(xin)電(dian)源監控(kong)系統,實(shi)時(shi)(shi)監控(kong)通(tong)信(xin)電(dian)源設(she)備的各種運行(xing)參數,發(fa)現問(wen)題及時(shi)(shi)處理。
2、電(dian)(dian)源巡視(shi)檢(jian)測內(nei)容(rong)。模(mo)塊(kuai)配置是(shi)否(fou)合理;充電(dian)(dian)限(xian)流值(zhi)是(shi)否(fou)正確(que)、有無告警;系統(tong)交流電(dian)(dian)壓、電(dian)(dian)流,直流浮充電(dian)(dian)壓、負(fu)載電(dian)(dian)流、蓄(xu)電(dian)(dian)池(chi)補(bu)充電(dian)(dian)電(dian)(dian)流、風扇運(yun)行狀(zhuang)(zhuang)況(kuang)(kuang)和防雷器件狀(zhuang)(zhuang)況(kuang)(kuang);監(jian)控模(mo)塊(kuai)的各項運(yun)行參數(shu)是(shi)否(fou)正確(que);溫(wen)度補(bu)償是(shi)否(fou)正常啟用;模(mo)塊(kuai)均流是(shi)否(fou)小于5%;蓄(xu)電(dian)(dian)池(chi)保險(xian)和連接條溫(wen)升;蓄(xu)電(dian)(dian)池(chi)是(shi)否(fou)爬酸、漏液(ye)、鼓(gu)肚等(deng)現(xian)象(xiang);機(ji)房環境溫(wen)度等(deng)。
3、利用(yong)電(dian)源監控(kong)系統對電(dian)源設備(bei)(bei)實時遠(yuan)程監控(kong),了解故(gu)(gu)障(zhang)現(xian)象,進行(xing)遠(yuan)程監控(kong)解決,協(xie)助現(xian)場處(chu)(chu)理(li)。處(chu)(chu)理(li)電(dian)源設備(bei)(bei)障(zhang)礙時,應首先初步判(pan)斷造成電(dian)源障(zhang)礙原因和故(gu)(gu)障(zhang)部位,然后(hou)采取相應的(de)方法和措施對電(dian)源故(gu)(gu)障(zhang)進行(xing)處(chu)(chu)理(li)。
4、在處(chu)理故(gu)障的(de)過程中應重(zhong)點關注以(yi)下幾(ji)方面問題(ti):
(1)一定(ding)要注(zhu)意不能引起直流輸出、交流輸入的短(duan)路,各種維(wei)護工(gong)具(ju)必須做好絕緣(yuan)處理,確保(bao)人(ren)身(shen)安全(quan)和電源設備供電的安全(quan)。
(2)在操作時應盡量單手(shou)操作,操作時手(shou)上(shang)(shang)、身上(shang)(shang)不(bu)允許帶有金屬導體的飾(shi)品,例如手(shou)表(biao)、鑰(yao)匙、戒指(zhi)等,同時穿上(shang)(shang)絕(jue)緣(yuan)鞋進行(xing)電(dian)源設(she)備維修。
(3)在處(chu)理電(dian)源(yuan)障礙的(de)過程中,尤其是小系統電(dian)源(yuan)設備的(de)二次下(xia)電(dian)功能一定要暫時取消,防(fang)止誤操(cao)作引(yin)起通(tong)信電(dian)源(yuan)系統的(de)供電(dian)中斷。
(4)在對交、直流配(pei)電系(xi)統不了(le)解(jie)的情況下,不要(yao)隨意或憑直覺(jue)打開(kai)(kai)(kai)或關閉交流供(gong)電開(kai)(kai)(kai)關,更不允許插、拔(ba)直流熔斷器和(he)關掉直流輸出空(kong)氣開(kai)(kai)(kai)關。