1、定期巡視檢測通信電(dian)源設(she)備(bei)(bei)。注(zhu)意機房環境溫(wen)度和設(she)備(bei)(bei)運行(xing)狀況,利(li)用通信電(dian)源監控系統,實(shi)時監控通信電(dian)源設(she)備(bei)(bei)的各種運行(xing)參數,發現問(wen)題(ti)及時處理。
2、電(dian)(dian)源巡視檢測內容。模(mo)塊(kuai)配置是否(fou)合理;充(chong)電(dian)(dian)限流(liu)(liu)值是否(fou)正(zheng)確、有無告(gao)警;系統交流(liu)(liu)電(dian)(dian)壓、電(dian)(dian)流(liu)(liu),直(zhi)流(liu)(liu)浮充(chong)電(dian)(dian)壓、負載(zai)電(dian)(dian)流(liu)(liu)、蓄電(dian)(dian)池(chi)補(bu)(bu)充(chong)電(dian)(dian)電(dian)(dian)流(liu)(liu)、風扇運行狀況(kuang)和防雷器(qi)件狀況(kuang);監控模(mo)塊(kuai)的各項運行參(can)數是否(fou)正(zheng)確;溫(wen)度補(bu)(bu)償是否(fou)正(zheng)常(chang)啟用;模(mo)塊(kuai)均流(liu)(liu)是否(fou)小于5%;蓄電(dian)(dian)池(chi)保(bao)險(xian)和連接(jie)條溫(wen)升;蓄電(dian)(dian)池(chi)是否(fou)爬酸、漏液、鼓(gu)肚等(deng)現象;機房環境溫(wen)度等(deng)。
3、利用(yong)電(dian)源監(jian)控系統對(dui)電(dian)源設(she)備實時遠程監(jian)控,了解(jie)故(gu)障(zhang)(zhang)現象,進行遠程監(jian)控解(jie)決,協助現場處(chu)理。處(chu)理電(dian)源設(she)備障(zhang)(zhang)礙時,應首先初(chu)步判斷造成電(dian)源障(zhang)(zhang)礙原因和故(gu)障(zhang)(zhang)部位,然(ran)后采(cai)取(qu)相應的方(fang)法和措施對(dui)電(dian)源故(gu)障(zhang)(zhang)進行處(chu)理。
4、在處(chu)理故障的過程中應重點關注以下幾方面問題:
(1)一定要注意不能引起直(zhi)流輸出、交流輸入的短路,各種(zhong)維護(hu)工(gong)具必須做好絕(jue)緣(yuan)處理(li),確保(bao)人身(shen)安(an)全和電(dian)源設備供電(dian)的安(an)全。
(2)在操(cao)(cao)作(zuo)時(shi)應盡量單手操(cao)(cao)作(zuo),操(cao)(cao)作(zuo)時(shi)手上、身上不允許帶有金(jin)屬導體的飾品,例如手表、鑰(yao)匙(chi)、戒指等,同時(shi)穿上絕(jue)緣鞋進行電源設(she)備維修。
(3)在處(chu)理(li)電源(yuan)(yuan)(yuan)障礙的過程中,尤其是小系統電源(yuan)(yuan)(yuan)設備(bei)的二次下電功能一定要暫時(shi)取消,防止誤操作(zuo)引起通信電源(yuan)(yuan)(yuan)系統的供電中斷。
(4)在對交、直(zhi)(zhi)流(liu)配電系(xi)統不了解的(de)情(qing)況下,不要(yao)隨意或(huo)憑直(zhi)(zhi)覺打開或(huo)關(guan)閉交流(liu)供電開關(guan),更不允(yun)許(xu)插(cha)、拔直(zhi)(zhi)流(liu)熔斷器和關(guan)掉直(zhi)(zhi)流(liu)輸出(chu)空氣開關(guan)。