一、避雷針的原理是什么
避雷針是根據尖端(duan)放電原理(li)制成的(de)(de)。避雷針是用來保護(hu)建筑物、高大樹木等避免雷擊的(de)(de)裝置。在被保護(hu)物頂端(duan)安裝一(yi)根接閃器,用符合規格導(dao)線與埋在地(di)(di)下的(de)(de)泄流地(di)(di)網連接起來。
以避雷針作(zuo)為接(jie)閃器的(de)防雷電(dian)(dian)(dian)(dian)原理是(shi):避雷針通過導(dao)線(xian)接(jie)入地下(xia),與地面形(xing)成(cheng)(cheng)等電(dian)(dian)(dian)(dian)位(wei)差,利用自身(shen)的(de)高度(du),使電(dian)(dian)(dian)(dian)場(chang)強度(du)增加到極限(xian)值的(de)雷電(dian)(dian)(dian)(dian)云電(dian)(dian)(dian)(dian)場(chang)發(fa)生(sheng)畸變,開始電(dian)(dian)(dian)(dian)離并下(xia)行先導(dao)放(fang)電(dian)(dian)(dian)(dian),避雷針在(zai)強電(dian)(dian)(dian)(dian)場(chang)作(zuo)用下(xia)產生(sheng)尖端放(fang)電(dian)(dian)(dian)(dian),形(xing)成(cheng)(cheng)向(xiang)(xiang)上(shang)先導(dao)放(fang)電(dian)(dian)(dian)(dian),兩者會合形(xing)成(cheng)(cheng)雷電(dian)(dian)(dian)(dian)通路(lu),隨之瀉入大地,達到避雷效果。實際(ji)上(shang),避雷針是(shi)引雷針,可將周圍的(de)雷電(dian)(dian)(dian)(dian)引來并提前放(fang)電(dian)(dian)(dian)(dian),將雷電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)流(liu)通過自身(shen)的(de)接(jie)地導(dao)體傳向(xiang)(xiang)地面,避免(mian)保護對(dui)象直接(jie)遭雷擊。
二、避雷針的保護范圍是多少
避(bi)雷(lei)針的工作(zuo)原理就其本質(zhi)而言,避(bi)雷(lei)針不(bu)是(shi)(shi)避(bi)雷(lei),而是(shi)(shi)利用其高(gao)聳空中的有利地位,把(ba)雷(lei)電(dian)(dian)引向自身,承(cheng)受(shou)雷(lei)擊。同(tong)時把(ba)雷(lei)電(dian)(dian)流泄入(ru)大地,起著保護(hu)(hu)其附近比它矮的建(jian)筑(zhu)物或(huo)設備免受(shou)雷(lei)擊的作(zuo)用。簡單(dan)一點說,一級(ji)保護(hu)(hu)是(shi)(shi)以(yi)30米(mi)為(wei)半(ban)徑、二級(ji)保護(hu)(hu)是(shi)(shi)45米(mi)為(wei)半(ban)徑、三級(ji)保護(hu)(hu)是(shi)(shi)60米(mi)為(wei)半(ban)徑做弧的保護(hu)(hu)范圍。
1、計算方法
避雷針的(de)保護半徑與高(gao)度(h)有關,以(yi)及與所現的(de)滾球半徑有關,D為(wei)滾球半徑(閃(shan)擊(ji)距離)。
第一類建筑物為D=30米、第二(er)類建(jian)筑(zhu)物為D=45米、第三類建筑物為D=60米。
2、保護范圍采用規范之計算公式:Rx=?{h(2hr-h)}-?{hx(2hr-hx)}。
(1)其中Rx為避雷針(zhen)在距離(li)地面hx米處的保護半徑(米)。
(2)hr為滾球(qiu)半(ban)徑,根據建(jian)筑物類別(bie)取值30、45、60。
(3)hx為被保(bao)護物的高度。
一般(ban)來說,避雷針越(yue)高,保(bao)護范圍(wei)就越(yue)大,保(bao)護效(xiao)果也越(yue)好,但考慮到避雷針建設的安全性(xing)和經(jing)濟性(xing),避雷針大多建設在35米-45米之間。