一、氣壓罐容積規格
氣壓罐根據容積(ji)分一般可以分為(wei):2L,4L,8L,12L,18L,24L,36L,50L,60L,80L,100L,150L,200L,300L,500L,750L,1000L,1500L,2000L,3000L,5000L,6000L,10000L。
氣(qi)壓罐(guan)根據外殼(ke)材質分(fen)一般分(fen)為碳鋼膨脹(zhang)罐(guan)和不銹鋼膨脹(zhang)罐(guan)。
二、氣壓罐有效容積要求
設置(zhi)穩壓泵(beng)的臨時(shi)高(gao)壓消防(fang)給水(shui)(shui)系(xi)統應設置(zhi)防(fang)止穩壓泵(beng)頻(pin)繁啟停(ting)的技術(shu)措施,當采用(yong)氣壓水(shui)(shui)罐時(shi),其調節容(rong)積應根據穩壓泵(beng)啟泵(beng)次數不(bu)大于15次/h計算確定,但有(you)效(xiao)儲水(shui)(shui)容(rong)積不(bu)宜小于150L。
氣壓(ya)罐有效(xiao)容積要求提示:
1、氣壓(ya)罐低置、放置于消防(fang)泵(beng)房(fang)時 P1>0.01H+0.15,且≥0.01H2+0.1,P2=P1/0.85
2、氣壓(ya)罐(guan)高(gao)置,放置于高(gao)位消防水箱間時(shi) P1>0.15-0.01H1,且≥0.01H2+0.07,P2=P1/0.8
3、氣壓罐調節容積有效儲水(shui)容積
4、氣壓罐總容積
式中:
Vq1——氣壓罐(guan)有(you)效儲水容積。
Vq——氣壓罐總容積。
β——氣(qi)壓(ya)罐(guan)(guan)容積(ji)系(xi)數,隔膜式氣(qi)壓(ya)罐(guan)(guan)取(qu)1.05。
——氣(qi)壓(ya)罐內工(gong)作(zuo)壓(ya)力比,宜采用(yong)0.65~0.85。
n每(mei)小時啟泵次數。
注:壓力的單位為MPa。
三、壓力儲罐容積和有效容積
關于(yu)壓(ya)力罐的容積(ji)和有(you)效(xiao)容積(ji)容易搞混淆,簡(jian)單點說就(jiu)是(shi)壓(ya)力罐安裝到系(xi)統后(hou),系(xi)統運(yun)(yun)行(xing)后(hou)和靜(jing)壓(ya)狀態(tai)未運(yun)(yun)行(xing)時(shi)壓(ya)力罐氣(qi)囊內容納的水(shui)的體(ti)積(ji)差,比如,系(xi)統運(yun)(yun)行(xing)后(hou)氣(qi)囊內水(shui)的體(ti)積(ji)是(shi)100L,靜(jing)壓(ya)狀態(tai)時(shi)氣(qi)囊內的水(shui)體(ti)積(ji)是(shi)20L,那么有(you)效(xiao)容積(ji)就(jiu)是(shi)100-20=80L。
壓(ya)(ya)力(li)罐的(de)有效容(rong)(rong)積跟(gen)工(gong)況和預(yu)充壓(ya)(ya)力(li)的(de)大小直接相關,相同(tong)體積的(de)壓(ya)(ya)力(li)罐,在不同(tong)工(gong)況或者不同(tong)預(yu)充壓(ya)(ya)力(li)的(de)情況下有效容(rong)(rong)積是不一樣的(de),在閉式循環系統(tong)和定(ding)(ding)壓(ya)(ya)系統(tong)也略(lve)有不同(tong),但(dan)基本都是按PV=定(ding)(ding)值來(lai)計算(suan),舉例說明:
閉式循環系(xi)統(tong)(tong)(tong)(tong)中(zhong)為(wei)了增加壓(ya)(ya)力(li)(li)罐(guan)的有效(xiao)容(rong)積,一般(ban)把壓(ya)(ya)力(li)(li)罐(guan)的預充(chong)壓(ya)(ya)力(li)(li)設置為(wei)跟系(xi)統(tong)(tong)(tong)(tong)靜(jing)(jing)壓(ya)(ya)一致,由(you)于(yu)系(xi)統(tong)(tong)(tong)(tong)工(gong)作介(jie)質壓(ya)(ya)力(li)(li)跟預充(chong)壓(ya)(ya)力(li)(li)大小一樣,此時(shi)工(gong)作介(jie)質恰好進不到氣(qi)囊內(nei);當系(xi)統(tong)(tong)(tong)(tong)開始運行后,氣(qi)囊內(nei)最多(duo)能吸(xi)收多(duo)少工(gong)作介(jie)質,取決于(yu)系(xi)統(tong)(tong)(tong)(tong)安全閥起跳壓(ya)(ya)力(li)(li),因為(wei)壓(ya)(ya)力(li)(li)總(zong)是往最容(rong)易去的地方(fang)去,當安全閥開始泄(xie)壓(ya)(ya)后,由(you)于(yu)泄(xie)壓(ya)(ya)口直接通著大氣(qi),介(jie)質不再進到氣(qi)囊內(nei),假設系(xi)統(tong)(tong)(tong)(tong)靜(jing)(jing)壓(ya)(ya)跟壓(ya)(ya)力(li)(li)罐(guan)預充(chong)壓(ya)(ya)力(li)(li)都是1.5bar,系(xi)統(tong)(tong)(tong)(tong)安全閥的起跳壓(ya)(ya)力(li)(li)為(wei)6bar,壓(ya)(ya)力(li)(li)罐(guan)的總(zong)容(rong)積為(wei)100L,由(you)PV=定值其有效(xiao)容(rong)積計算如下(xia):
P0*V0=P1*V1 V1=P0*V0/P1
P0=1.5bar V0=100L(忽略氣囊的體積(ji),預(yu)充氣體的體積(ji)就等于罐(guan)的體積(ji))P1=6bar
V1=P0*V0/P1=1.5*100/6=25L
即當(dang)安全(quan)閥即將泄(xie)壓(ya)時(shi),壓(ya)力(li)罐(guan)氣(qi)囊(nang)(nang)跟(gen)罐(guan)體(ti)(ti)間預(yu)(yu)充氣(qi)體(ti)(ti)的(de)體(ti)(ti)積(ji)被壓(ya)縮到只有(you)25L,那么氣(qi)囊(nang)(nang)內工作介質的(de)體(ti)(ti)積(ji)等于(yu)罐(guan)的(de)體(ti)(ti)積(ji)減預(yu)(yu)充氣(qi)體(ti)(ti)的(de)體(ti)(ti)積(ji),也(ye)就(jiu)是100-25=75L。由(you)以(yi)上計算過(guo)程可知,當(dang)系統安全(quan)閥起跳壓(ya)力(li)不(bu)(bu)一(yi)樣(yang),有(you)效容積(ji)就(jiu)不(bu)(bu)一(yi)樣(yang),同樣(yang)的(de)道理,如果(guo)預(yu)(yu)充壓(ya)力(li)跟(gen)系統靜壓(ya)不(bu)(bu)一(yi)樣(yang)大(da),結果(guo)也(ye)不(bu)(bu)一(yi)樣(yang)。
在定壓系統中為了限度的利用壓力罐的有效容積,一般把水泵的啟泵壓力跟壓力罐的預充壓力設置成一致,這樣當系統缺水時,壓力罐氣囊內的水全部補充到系統正好水泵開始啟動,避免了壓力罐氣囊內還有水未利用到水泵就啟動了,水泵的停泵壓力相當于閉式循環系統里面安全閥的起跳壓力一樣,計算過程跟上面的類似,所以預充壓力、啟泵、停泵壓力不一樣,同樣大小的壓力罐,有效容積就不一樣大,所以盲目在壓力罐上標注有效容積的做(zuo)法是(shi)錯誤(wu)的。