一、三相多功能電力儀表校驗方法
多功能電力儀表應(ying)定期進行校(xiao)(xiao)驗,保證測(ce)量的準確性,具體的校(xiao)(xiao)驗方法步驟如(ru)下:
1、校驗前
(1)查看多功能電力儀表是否(fou)接入儀表(biao)電源(yuan)(yuan),有無(wu)示數(shu)。若(ruo)無(wu)示數(shu)顯示,則檢查(cha)電源(yuan)(yuan)線,控制(zhi)電源(yuan)(yuan)回路。
(2)外(wai)觀檢查,檢查是(shi)否有(you)缺角,看是(shi)否有(you)零件(jian)脫落(luo)或(huo)損壞之處,緊固件(jian)是(shi)否松動,電路連接線是(shi)否開焊等顯示不正常情(qing)況。
(3)記錄下該多功(gong)能(neng)電(dian)力儀(yi)表的銘牌,包(bao)括生(sheng)產日期(qi)、廠家、精度(du)、出廠日期(qi)、編(bian)號、變比、型號、天氣情(qing)況(kuang)、環(huan)境(jing)溫度(du)、環(huan)境(jing)濕(shi)度(du)等(deng)。二(er)次回路(lu)清(qing)掃檢(jian)查,電(dian)流表CT,電(dian)壓表PT,功(gong)率表PT/CT二(er)次側(ce)回路(lu)清(qing)掃,檢(jian)查。
2、主要參數校驗過程
(1)原理
次級(ji)線(xian)圈(quan)的(de)額(e)定電壓(ya)一(yi)般設計為100V,與其配套(tao)使(shi)用(yong)的(de)交流(liu)電壓(ya)表量(liang)程也應為100V,通過變(bian)比換(huan)算(suan)(suan)出(chu)一(yi)次側(ce)線(xian)電壓(ya)的(de)標準值(zhi)(zhi)。次級(ji)線(xian)圈(quan)的(de)額(e)定電流(liu)一(yi)般設計為5A,與其配套(tao)使(shi)用(yong)的(de)交流(liu)電流(liu)表量(liang)程也應為5A,通過變(bian)比換(huan)算(suan)(suan)出(chu)一(yi)次側(ce)相電流(liu)的(de)標準值(zhi)(zhi),然后(hou)根據(ju)電流(liu)電壓(ya),換(huan)算(suan)(suan)出(chu)有功(gong)功(gong)率,無功(gong)功(gong)率等。
(2)電壓校驗
按(an)照多(duo)功(gong)能電(dian)力(li)儀(yi)(yi)(yi)表(biao)(biao)(biao)說明書正(zheng)確設置儀(yi)(yi)(yi)表(biao)(biao)(biao)參數(shu),在(zai)校驗裝(zhuang)置上(shang)輸(shu)入”11.547U”然(ran)后按(an)“Enter”鍵,則此時裝(zhuang)置對多(duo)功(gong)能電(dian)力(li)儀(yi)(yi)(yi)表(biao)(biao)(biao)ABC三相輸(shu)入11.547V相電(dian)壓(ya),二次線電(dian)壓(ya)為20V。操作多(duo)功(gong)能電(dian)力(li)儀(yi)(yi)(yi)表(biao)(biao)(biao)到電(dian)壓(ya)顯示(shi)界面,記(ji)錄下多(duo)功(gong)能電(dian)力(li)儀(yi)(yi)(yi)表(biao)(biao)(biao)線電(dian)壓(ya)顯示(shi)數(shu)據。然(ran)后按(an)照上(shang)述方法分別,在(zai)檢(jian)測裝(zhuang)置輸(shu)入23.094U,34.642U,46.189U,57.737U,記(ji)錄多(duo)功(gong)能電(dian)力(li)儀(yi)(yi)(yi)表(biao)(biao)(biao)線電(dian)壓(ya)顯示(shi)數(shu)據。
(3)電流校驗
檢測裝(zhuang)置上先按(an)(an)(an)Menu鍵(jian)進入(ru)(ru)主菜單,然(ran)后(hou)(hou)按(an)(an)(an)“1交(jiao)流(liu)(liu)輸出“進入(ru)(ru)交(jiao)流(liu)(liu)輸出界面,按(an)(an)(an)V/Y鍵(jian),用于Y型或V型接線方式選擇(ze),一般多(duo)(duo)數為(wei)Y型接法,按(an)(an)(an)IRange量程(cheng)鍵(jian)選擇(ze)合(he)適量程(cheng),一般電流(liu)(liu)互(hu)感器二(er)次側電流(liu)(liu)為(wei)5A。輸入(ru)(ru)”1I”然(ran)后(hou)(hou)按(an)(an)(an)Enter鍵(jian),則此時裝(zhuang)置對儀表(biao)ABC三(san)相(xiang)輸入(ru)(ru)1安培(pei)電流(liu)(liu),調節多(duo)(duo)功能電力(li)儀表(biao)到電流(liu)(liu)顯示(shi)(shi)界面,記錄下多(duo)(duo)功能電力(li)儀表(biao)顯示(shi)(shi)數據。然(ran)后(hou)(hou)按(an)(an)(an)照(zhao)上述(shu)方法,分(fen)別輸入(ru)(ru)2I,3I,4I,5I,記錄下多(duo)(duo)功能電力(li)儀表(biao)顯示(shi)(shi)數據。
(4)有功功率,無功功率,功率因素校驗
A、有功(gong)(gong)(gong)(gong)功(gong)(gong)(gong)(gong)率(lv)(lv):在檢測裝(zhuang)置(zhi)(zhi)上(shang)選擇(ze)好電(dian)(dian)壓(ya)電(dian)(dian)流(liu)(liu)相(xiang)對應的量程和接線(xian)方式,輸(shu)(shu)入(ru)57.737U然后按Enter鍵(jian)(jian)。按快捷(jie)鍵(jian)(jian)區(qu)“Φ試驗點(dian)1.0”,調整儀(yi)表功(gong)(gong)(gong)(gong)率(lv)(lv)為有功(gong)(gong)(gong)(gong)功(gong)(gong)(gong)(gong)率(lv)(lv)模(mo)式,輸(shu)(shu)入(ru)”1I”然后按Enter鍵(jian)(jian),則此(ci)時(shi)裝(zhuang)置(zhi)(zhi)對多功(gong)(gong)(gong)(gong)能電(dian)(dian)力儀(yi)表ABC三相(xiang)輸(shu)(shu)入(ru)1安(an)培電(dian)(dian)流(liu)(liu),線(xian)電(dian)(dian)壓(ya)100V。調節多功(gong)(gong)(gong)(gong)能電(dian)(dian)力儀(yi)表到有功(gong)(gong)(gong)(gong)功(gong)(gong)(gong)(gong)率(lv)(lv)顯(xian)示(shi)界面,記錄(lu)下數據。然后按照上(shang)述方法,分(fen)別輸(shu)(shu)入(ru)2I,3I,4I,5I,記錄(lu)下數據。
B、無功(gong)(gong)功(gong)(gong)率(lv)(lv):在(zai)檢(jian)測裝置上(shang)按快捷鍵區“Φ試驗點(dian)0.0L”或“Φ試驗點(dian)0.0C”調整多(duo)功(gong)(gong)能電力(li)儀(yi)表(biao)功(gong)(gong)率(lv)(lv)為無功(gong)(gong)功(gong)(gong)率(lv)(lv)模式,然后在(zai)分別(bie)輸入1I、2I、3I、4I、5I,調節多(duo)功(gong)(gong)能電力(li)儀(yi)表(biao)到無功(gong)(gong)功(gong)(gong)功(gong)(gong)率(lv)(lv)顯示界(jie)面,記錄下數據。
C、功率因素(su):在檢測裝置上(shang)分別(bie)按快(kuai)捷(jie)鍵區(qu)“Φ試(shi)(shi)驗(yan)點0.0L”、“Φ試(shi)(shi)驗(yan)點0.5L”、“試(shi)(shi)驗(yan)點1.0”、“Φ試(shi)(shi)驗(yan)點0.8C”、“Φ試(shi)(shi)驗(yan)點0.5C”、“Φ試(shi)(shi)驗(yan)點0.0C”,調節(jie)多功能(neng)電力儀(yi)表到(dao)功率因素(su)顯示界面,記(ji)錄下數據。
3、校驗后
(1)對電源控制(zhi)回路經(jing)行檢(jian)查,由于實驗(yan)所斷(duan)開的控制(zhi)開關,拔掉(diao)的熔絲,都要經(jing)行復歸。
(2)對于直接(jie)加線(xian)到(dao)多功能電力儀表上的(de)實(shi)(shi)驗(yan)(yan),實(shi)(shi)驗(yan)(yan)后要注(zhu)意(yi)復(fu)歸過(guo)功能電力儀表上的(de)原來(lai)所脫開的(de)導(dao)線(xian),保證接(jie)線(xian)正確(que)。
(3)對于端子排上電壓,電流(liu)回(hui)路進(jin)行(xing)檢查,由于實驗所(suo)拆的滑片,導(dao)線都要經(jing)行(xing)復歸。
二、多功能電力儀表校驗常見問題及處理方法
多功能電力(li)儀表校驗(yan)過程中,可能會(hui)遇到一(yi)些(xie)問(wen)題(ti),下(xia)(xia)面為大(da)家介(jie)紹一(yi)下(xia)(xia)這(zhe)些(xie)問(wen)題(ti)的處理方法:
1、為(wei)了檢測儀表回路,一(yi)(yi)般情況下先(xian)從端子排上進行實驗。因此要注意通過變壓器(qi)二次側向(xiang)(xiang)一(yi)(yi)次側反向(xiang)(xiang)送(song)電,必須先(xian)把相對應的電壓二次側回路斷(duan)開。一(yi)(yi)般也要在端子排上把電流互感(gan)器(qi)二次測的回路滑(hua)片脫開。
2、進行電壓(ya)校驗時,注意(yi)電壓(ya)回路是否有電器元件導(dao)致所加的電壓(ya)分壓(ya),造成(cheng)數據的誤差。
3、若(ruo)端子排線(xian)路復(fu)雜,無法(fa)進行(xing)試驗,則(ze)可以直接把電(dian)壓,電(dian)流加在(zai)儀表上(shang),應注意要脫開外電(dian)路,所加電(dian)壓線(xian)的觸頭應該(gai)保持一定(ding)間隙,防止(zhi)短路。
4、若(ruo)發現所測電(dian)(dian)(dian)壓,電(dian)(dian)(dian)流數據有微(wei)小波動(dong)時(shi),因先(xian)檢查是(shi)否所加頻率是(shi)50Hz,然(ran)后先(xian)把電(dian)(dian)(dian)壓,電(dian)(dian)(dian)流加到滿(man)量程,一般情況(kuang)下可以消除波動(dong)。
5、若(ruo)發現(xian)所(suo)測的(de)(de)電(dian)壓(ya),電(dian)流,有(you)功,無功的(de)(de)值與(yu)標(biao)準值有(you)明顯差異時,因先檢查是(shi)否(fou)(fou)是(shi)回路問題,加錯(cuo)線或者(zhe)相序弄等,然(ran)后在檢查是(shi)否(fou)(fou)是(shi)該(gai)表變比問題,與(yu)之前所(suo)記錄的(de)(de)電(dian)壓(ya)互(hu)感器、電(dian)流互(hu)感器變比,進行比較。若(ruo)設(she)(she)置(zhi)(zhi)錯(cuo)誤(wu),則對多功能(neng)電(dian)力儀表進行設(she)(she)置(zhi)(zhi),設(she)(she)置(zhi)(zhi)正確后,在進行校驗。
6、若發現所測電(dian)流(liu)表(biao),功率表(biao)是顯示負數,則要檢(jian)查是否是所加電(dian)流(liu)極性錯誤。