一、消防泵的作用
消(xiao)(xiao)防泵是(shi)用來(lai)抽送各類液(ye)體,是(shi)創建無泄(xie)漏(lou)、無污染文(wen)明(ming)車間(jian)、文(wen)明(ming)工廠的理(li)(li)想用泵與消(xiao)(xiao)防系統(tong)的。以它(ta)全密封(feng)、無泄(xie)漏(lou)、耐(nai)腐蝕之(zhi)特點,廣泛(fan)應用于環保、水處(chu)理(li)(li)、消(xiao)(xiao)防等部門。
二、消防水泵安裝注意事項
1、消防水泵安裝前應校核消防泵品牌產(chan)品合格(ge)證,以及其規格(ge)、型號和性能與(yu)設(she)計要求應一致(zhi),并(bing)應根據安(an)(an)裝使(shi)用說明書安(an)(an)裝。
2、消防(fang)水泵(beng)安裝前應(ying)復核(he)水泵(beng)基(ji)礎(chu)混(hun)凝土強(qiang)度、隔(ge)振裝置、坐標、標高、尺寸和(he)螺栓孔位(wei)置。
3、消(xiao)防水泵的安(an)裝應符合現行國家(jia)標準(zhun)《機械(xie)設(she)備安(an)裝工(gong)(gong)(gong)程(cheng)施工(gong)(gong)(gong)及驗收(shou)(shou)通用規(gui)(gui)范(fan)》GB50231和《風機、壓(ya)縮機、泵安(an)裝工(gong)(gong)(gong)程(cheng)施工(gong)(gong)(gong)及驗收(shou)(shou)規(gui)(gui)范(fan)》GB50275的有關規(gui)(gui)定。
4、消防(fang)水(shui)泵安(an)裝前應(ying)(ying)復核(he)消防(fang)水(shui)泵之間,以及消防(fang)水(shui)泵與墻(qiang)或(huo)其(qi)他設備(bei)之間的間距,并(bing)應(ying)(ying)滿足安(an)裝、運行和維護(hu)管理的要(yao)求。
5、消(xiao)防水泵(beng)吸水管上(shang)的控(kong)制(zhi)閥應(ying)(ying)(ying)(ying)在消(xiao)防水泵(beng)固定于基礎上(shang)后在進行(xing)安(an)裝,其直徑不應(ying)(ying)(ying)(ying)小于消(xiao)防水泵(beng)吸水口直徑,且不應(ying)(ying)(ying)(ying)采用(yong)沒(mei)有可靠鎖定裝置的控(kong)制(zhi)閥,控(kong)制(zhi)閥應(ying)(ying)(ying)(ying)采用(yong)溝漕(cao)式或(huo)法蘭(lan)式閥門。
6、當消防水泵(beng)和消防水池位于獨(du)立的兩(liang)個(ge)基礎(chu)上且相互為剛性連(lian)接時,吸水管上應(ying)加設柔性連(lian)接管。
7、吸水管水平管段上不應(ying)有氣(qi)囊和(he)漏(lou)氣(qi)現(xian)象(xiang)。變徑連(lian)接時,應(ying)采用偏(pian)心異(yi)徑管件并應(ying)采用管頂平接。
8、消防水(shui)(shui)泵出水(shui)(shui)管上(shang)應安裝(zhuang)消聲止回閥、控制閥和(he)(he)壓(ya)力表(biao)(biao);系統的(de)總出水(shui)(shui)管上(shang)還應安裝(zhuang)壓(ya)力表(biao)(biao)和(he)(he)壓(ya)力開(kai)關;安裝(zhuang)壓(ya)力表(biao)(biao)時應加設緩(huan)沖(chong)裝(zhuang)置。壓(ya)力表(biao)(biao)和(he)(he)緩(huan)沖(chong)裝(zhuang)置之間應安裝(zhuang)旋塞(sai);壓(ya)力表(biao)(biao)量(liang)程在沒有(you)設計要求時,應為(wei)系統工作壓(ya)力的(de)2倍(bei)---2、5倍(bei)。
9、消(xiao)防水泵的隔振裝置、進水管柔性(xing)接頭(tou)的安(an)裝應符(fu)合設計要求,并應有產品說明(ming)和安(an)裝使用(yong)說明(ming)。
三、消防泵怎么啟動
消(xiao)(xiao)(xiao)防(fang)控(kong)制(zhi)室與消(xiao)(xiao)(xiao)火(huo)栓(shuan)動作按鈕啟(qi)動關(guan)系與消(xiao)(xiao)(xiao)火(huo)栓(shuan)泵的(de)(de)(de)啟(qi)動形式(shi)(shi)有關(guan)。消(xiao)(xiao)(xiao)防(fang)泵的(de)(de)(de)啟(qi)動方式(shi)(shi)一(yi)般分為(wei)兩種,第(di)一(yi)種啟(qi)動方式(shi)(shi)是在(zai)總線(xian)制(zhi)聯控(kong)方式(shi)(shi)下,消(xiao)(xiao)(xiao)火(huo)栓(shuan)動作按鈕的(de)(de)(de)起動可通過設在(zai)消(xiao)(xiao)(xiao)火(huo)栓(shuan)旁(pang)的(de)(de)(de)聯動接口模塊將(jiang)其要求(qiu)的(de)(de)(de)啟(qi)動信號送(song)至消(xiao)(xiao)(xiao)防(fang)控(kong)制(zhi)室控(kong)制(zhi)臺,再從此處(chu)輸出使消(xiao)(xiao)(xiao)火(huo)栓(shuan)啟(qi)動的(de)(de)(de)開關(guan)量觸點。
第二種(zhong)啟動(dong)(dong)(dong)方(fang)式(shi),是直接將消火(huo)栓(shuan)動(dong)(dong)(dong)作按鈕的(de)(de)開關量(liang)觸(chu)點輸出到(dao)消火(huo)栓(shuan)泵啟動(dong)(dong)(dong)箱。這兩種(zhong)啟動(dong)(dong)(dong)方(fang)式(shi)在實(shi)(shi)際(ji)設(she)計(ji)中都可(ke)以運用(yong)(yong),前一種(zhong)方(fang)式(shi)接線省,但需(xu)在總線制下,對消火(huo)栓(shuan)聯動(dong)(dong)(dong)模塊進行(xing)地址編碼編程(cheng)來達到(dao)監測(ce)大(da)量(liang)消火(huo)栓(shuan)的(de)(de)目的(de)(de)。后一種(zhong)啟動(dong)(dong)(dong)方(fang)式(shi)簡單(dan)可(ke)靠(kao),但還(huan)需(xu)要把消火(huo)栓(shuan)動(dong)(dong)(dong)作信(xin)號返(fan)給(gei)消防控制室。設(she)計(ji)者在具體設(she)計(ji)中可(ke)根據實(shi)(shi)際(ji)工程(cheng)規模大(da)小來選用(yong)(yong),工程(cheng)規模大(da)、建筑形式(shi)復(fu)雜可(ke)采(cai)用(yong)(yong)前一種(zhong)啟動(dong)(dong)(dong)方(fang)式(shi),規模小可(ke)采(cai)用(yong)(yong)后一種(zhong)啟動(dong)(dong)(dong)方(fang)式(shi)。
消(xiao)防泵(beng)的自啟(qi)動(dong)(dong)是通(tong)過(guo)各保護區的管(guan)網噴(pen)嘴玻璃球高(gao)溫下爆碎,引起管(guan)網水(shui)流流動(dong)(dong),從(cong)而聯動(dong)(dong)報警(jing)閥(fa)壓力開(kai)關(guan)動(dong)(dong)作(zuo),達到自啟(qi)動(dong)(dong)噴(pen)淋(lin)(lin)泵(beng)的目的。通(tong)過(guo)水(shui)流指(zhi)示(shi)器聯動(dong)(dong)模塊或報警(jing)閥(fa)壓力開(kai)關(guan)引線至(zhi)控(kong)(kong)制(zhi)室(shi),消(xiao)防控(kong)(kong)制(zhi)室(shi)能準確反映(ying)其動(dong)(dong)作(zuo)信號,同時(shi)控(kong)(kong)制(zhi)室(shi)應能直(zhi)接(jie)控(kong)(kong)制(zhi)噴(pen)淋(lin)(lin)泵(beng)啟(qi)停。