一、消防報警系統原理有哪些
1、自動報警系統的工作原理
火(huo)災(zai)自(zi)動(dong)報(bao)(bao)警(jing)(jing)系統(tong)應(ying)由觸(chu)發裝置、災(zai)報(bao)(bao)警(jing)(jing)裝置、災(zai)警(jing)(jing)報(bao)(bao)裝置和電源等四部分組成(cheng),火(huo)災(zai)報(bao)(bao)警(jing)(jing)大(da)致過(guo)程:當煙(yan)、溫度、光、氣體濃度等火(huo)場(chang)參數超過(guo)某一給定閾值時,火(huo)災(zai)探(tan)測器動(dong)作(zuo)(zuo),發出報(bao)(bao)警(jing)(jing)號,該(gai)信(xin)號經過(guo)連接導(dao)線傳送至(zhi)區域火(huo)災(zai)報(bao)(bao)警(jing)(jing)控(kong)制器和(或)集中(zhong)火(huo)災(zai)報(bao)(bao)警(jing)(jing)控(kong)制器,發出聲、光報(bao)(bao)警(jing)(jing)信(xin)號,同時顯(xian)示火(huo)災(zai)發生的部位,以通知消防值班人員做出反應(ying),這(zhe)也就是我們通常所說的火(huo)災(zai)自(zi)動(dong)報(bao)(bao)警(jing)(jing)系統(tong)的工(gong)作(zuo)(zuo)原理。
2、防排煙系統的工作原理
當發(fa)生災后,操作機構(gou)在煙(yan)感報警(jing)電信號作用下,將風(feng)(feng)閥(fa)自動(dong)打(da)開,并啟(qi)(qi)動(dong)送風(feng)(feng)機與排煙(yan)風(feng)(feng)機,當排煙(yan)管(guan)內的氣(qi)流達到280°C時,管(guan)道防火閥(fa)熔(rong)斷器熔(rong)斷。關閉防火閥(fa),關閉信號通過輸(shu)入(ru)模塊(kuai)發(fa)送至控制器,自動(dong)或手動(dong)啟(qi)(qi)動(dong)相應控制模塊(kuai)去關閉排煙(yan)機。
在(zai)有空調設備時,空調送風管(guan)道內的氣流(liu)溫度達(da)到70°C時,防火(huo)熔(rong)斷器動作,關閉(bi)(bi)防火(huo)閥,關閉(bi)(bi)信號通(tong)過輸(shu)入模塊傳送至控(kong)制器,控(kong)制器則(ze)根(gen)據聯動關系給控(kong)制模塊信號,關閉(bi)(bi)空調機。
3、泡沫系統的工作原理
(1)閉式泡(pao)沫噴淋滅(mie)火系(xi)統工(gong)作(zuo)原理
當有(you)(you)火災發生時(shi),閉式噴頭(tou)的玻璃球破裂噴水,水流(liu)指示(shi)器、濕式報警閥動(dong)作(zuo)(zuo),有(you)(you)信號(hao)傳至控制柜,此(ci)時(shi),手動(dong)或自動(dong)開(kai)啟消(xiao)防(fang)泵比例混(hun)(hun)合(he)裝置(zhi)上的電磁(ci)閥及(ji)管路閥門(men),系統(tong)工作(zuo)(zuo)。一(yi)定壓力的消(xiao)防(fang)水經泡(pao)沫(mo)比例混(hun)(hun)合(he)裝置(zhi)與泡(pao)沫(mo)液(ye)混(hun)(hun)合(he),形成一(yi)定比例的泡(pao)沫(mo)混(hun)(hun)合(he)液(ye),經噴頭(tou)生成空氣泡(pao)沫(mo)滅(mie)火。
系統組成:閉式泡(pao)沫噴淋滅火系統主(zhu)要由(you)消防水泵泡(pao)沫比例混合裝置、閉式噴頭、水流指(zhi)示器、濕式報警閥(fa)及(ji)其它閥(fa)門(men)、管道等組成。
(2)開式(shi)泡沫噴淋滅火系統的工(gong)作原理
當有(you)火災發生時(shi),安裝(zhuang)于(yu)保(bao)護區的火災探測器有(you)信號傳至控制柜,此時(shi),手動或自動開啟雨(yu)淋(lin)閥、消(xiao)防(fang)泵(beng)比例混(hun)(hun)合器上(shang)的電(dian)磁(ci)閥及管路閥門,系統工作(zuo)。壓力消(xiao)防(fang)水經泡(pao)(pao)沫比例混(hun)(hun)合裝(zhuang)置與泡(pao)(pao)沫液混(hun)(hun)合,形(xing)成一(yi)定比例的泡(pao)(pao)沫混(hun)(hun)合液,經噴(pen)頭生成空(kong)氣(qi)泡(pao)(pao)沫滅火。
系(xi)統組成(cheng)(cheng):開式(shi)泡沫(mo)噴淋滅(mie)火系(xi)統主要由消防水泵、泡沫(mo)比例混合裝置、開式(shi)噴頭、雨(yu)淋閥及(ji)其它(ta)閥門、管道(dao)等(deng)組成(cheng)(cheng)。
4、室內外消火栓系統的工作原理
消(xiao)火栓開啟,有(you)水噴出,恒壓(ya)(ya)泵(beng)啟動,恒壓(ya)(ya)對管(guan)(guan)網補壓(ya)(ya),按(an)(an)下(xia)破玻按(an)(an)鈕,消(xiao)防(fang)(fang)中心收到(dao)(dao)破玻按(an)(an)鈕報警(jing)信(xin)號,警(jing)鈴(ling)鳴響,直(zhi)接(jie)啟動主消(xiao)防(fang)(fang)水泵(beng),消(xiao)防(fang)(fang)水泵(beng)對管(guan)(guan)網進(jin)行加壓(ya)(ya),消(xiao)火栓上的啟泵(beng)指示燈亮(liang)。消(xiao)防(fang)(fang)中心收到(dao)(dao)消(xiao)防(fang)(fang)水泵(beng)運行信(xin)號。
因(yin)水(shui)泵(beng)壞或水(shui)池(chi)無水(shui)時,消(xiao)(xiao)(xiao)防(fang)車對水(shui)泵(beng)接合器進行加(jia)壓,保證(zheng)消(xiao)(xiao)(xiao)防(fang)系(xi)統(tong)能正常(chang)運(yun)行。(水(shui)泵(beng)能手動(dong)(dong)啟動(dong)(dong),消(xiao)(xiao)(xiao)防(fang)中心手動(dong)(dong)啟動(dong)(dong)、自動(dong)(dong)啟動(dong)(dong))。
5、自動滅火系統的工作原理
噴淋頭達到(dao)額(e)定溫度(du)時,玻璃(li)內(nei)的液體(ti)發熱膨(peng)脹,玻璃(li)管(guan)破(po)碎,噴淋頭噴水(shui)(shui)(shui),水(shui)(shui)(shui)流指示(shi)器(qi)(qi)報警(jing)(jing),消防中(zhong)(zhong)(zhong)心收(shou)到(dao)報警(jing)(jing)信(xin)號(hao),力(li)下降(jiang),水(shui)(shui)(shui)池(chi)或(huo)恒壓(ya)(ya)(ya)泵(beng)(beng)補壓(ya)(ya)(ya),濕式報警(jing)(jing)閥動作,水(shui)(shui)(shui)力(li)警(jing)(jing)鐘(zhong)鳴(ming)響,壓(ya)(ya)(ya)力(li)開(kai)關(guan)報警(jing)(jing),消防中(zhong)(zhong)(zhong)心收(shou)報警(jing)(jing)信(xin)號(hao),水(shui)(shui)(shui)泵(beng)(beng)起泵(beng)(beng)加壓(ya)(ya)(ya)。消防中(zhong)(zhong)(zhong)心收(shou)到(dao)噴淋泵(beng)(beng)運(yun)(yun)行信(xin)號(hao)。因水(shui)(shui)(shui)泵(beng)(beng)壞或(huo)水(shui)(shui)(shui)池(chi)無水(shui)(shui)(shui)時,消防車(che)對水(shui)(shui)(shui)泵(beng)(beng)接合(he)器(qi)(qi)進行加壓(ya)(ya)(ya),保證消防系統(tong)能正常運(yun)(yun)行。(水(shui)(shui)(shui)泵(beng)(beng)能手(shou)動啟(qi)(qi)動,消防中(zhong)(zhong)(zhong)心手(shou)動啟(qi)(qi)動、自(zi)動啟(qi)(qi)動)。
6、氣體自動滅火系統的工作原理
感(gan)煙或(huo)感(gan)溫探(tan)測器任一報警(jing),主(zhu)機收到信號,警(jing)鐘(zhong)鳴(ming)響,感(gan)煙與感(gan)溫探(tan)測器同時(shi)報警(jing),主(zhu)機收到信號,警(jing)鐘(zhong)鳴(ming)響,光報警(jing)器鳴(ming)響。30S后聯(lian)動(dong)風閥(fa)、停(ting)空(kong)調新風機等(deng)、啟動(dong)氣體進(jin)行(xing)滅(mie)火(因誤報時(shi)在30S內(nei)按(an)下門(men)口或(huo)主(zhu)機上(shang)(shang)的(de)(de)急停(ting)按(an)鈕(niu)停(ting)止放(fang)氣)。人員發現火災(zai)時(shi),直(zhi)接按(an)下門(men)口或(huo)主(zhu)機上(shang)(shang)的(de)(de)緊急放(fang)氣按(an)鈕(niu),直(zhi)接聯(lian)動(dong)風閥(fa)、停(ting)空(kong)調新風機等(deng)啟動(dong)氣體進(jin)行(xing)滅(mie)火。
因(yin)主機(ji)不能正(zheng)常啟動(dong)氣體滅火時,直按用機(ji)械啟動(dong)氣體進行滅火。
7、防火卷簾的工作原理
在火(huo)災(zai)發(fa)(fa)生時(shi)起(qi)(qi)防(fang)火(huo)分區隔斷作用,在火(huo)災(zai)發(fa)(fa)生時(shi),感煙探(tan)測器報警(jing)(jing),災(zai)信號(hao)(hao)送到(dao)(dao)卷簾門制(zhi)柜,控制(zhi)柜發(fa)(fa)出啟動信號(hao)(hao),卷簾門自(zi)動降(jiang)到(dao)(dao)距(ju)地1.8米的位(wei)置(特殊部位(wei)的卷簾門也可一(yi)步到(dao)(dao)底(di)),如果(guo)感溫探(tan)測器再(zai)報警(jing)(jing),卷簾門才降(jiang)到(dao)(dao)底(di)。報警(jing)(jing)狀態(tai)時(shi),人員可手動按住上行按鈕升起(qi)(qi)卷簾,人過去后放開(kai)按鈕后防(fang)火(huo)門又自(zi)動下行。
8、消防廣播的工作原理
當火災(zai)(zai)發(fa)生時,災(zai)(zai)區(qu)域/層(如n層)的消(xiao)防煙感溫感等探測器發(fa)出報警動(dong)作信(xin)號(hao),消(xiao)防接(jie)收控制盤、邏輯控制等消(xiao)防聯(lian)動(dong)裝置(zhi)自動(dong)(或手動(dong))啟動(dong),通(tong)過消(xiao)防發(fa)送(song)控制盤發(fa)出驅動(dong)和切換控制信(xin)號(hao)。
一路去啟動消防廣播錄放盤,該盤可選(xuan)擇播音卡播音或話(hua)筒播音作為緊急廣播,并可自動錄音。
9、恒壓泵的工作原理
當管網泄(xie)漏、系(xi)統(tong)壓(ya)力降至設定壓(ya)力下限(xian)時(shi),穩壓(ya)水(shui)泵自動(dong)啟動(dong),對管網進行補壓(ya),以供(gong)消(xiao)防(fang)(fang)供(gong)水(shui)系(xi)統(tong)保證(zheng)最不利點的消(xiao)防(fang)(fang)所需壓(ya)力,當系(xi)統(tong)壓(ya)力達到設定壓(ya)力上限(xian)時(shi)穩泵停止(zhi)工(gong)作,每(mei)次壓(ya)力下降時(shi),都重復上述遠(yuan)行過程,以穩定消(xiao)防(fang)(fang)管網的壓(ya)力。
消防(fang)(fang)用(yong)水時(shi)(shi),穩壓(ya)(ya)(ya)泵(beng)持續運行(xing)(xing)阻(zu)懷(huai)壓(ya)(ya)(ya)力的(de)下降,當力降到消防(fang)(fang)主(zhu)泵(beng)啟(qi)(qi)動(dong)(dong)壓(ya)(ya)(ya)力時(shi)(shi),電控系(xi)(xi)統(tong)發出報警(jing)信號,啟(qi)(qi)動(dong)(dong)消防(fang)(fang)主(zhu)泵(beng)進行(xing)(xing)供水,當消防(fang)(fang)主(zhu)泵(beng)運行(xing)(xing)到達額定(ding)流量種壓(ya)(ya)(ya)力時(shi)(shi),控制系(xi)(xi)統(tong)關閉主(zhu)泵(beng)穩壓(ya)(ya)(ya)水運行(xing)(xing),當單臺(tai)消防(fang)(fang)泵(beng)運行(xing)(xing)機(ji)制信用(yong)證阻(zu)止不(bu)住壓(ya)(ya)(ya)力下降,系(xi)(xi)統(tong)壓(ya)(ya)(ya)力降至消防(fang)(fang)最(zui)低壓(ya)(ya)(ya)力時(shi)(shi),消防(fang)(fang)備用(yong)泵(beng)啟(qi)(qi)動(dong)(dong)(有兩(liang)主(zhu)一備時(shi)(shi))。
二、消防報警器怎么安裝
近期民用(yong)住宅(zhai)安(an)裝火(huo)災報(bao)警(jing)器的(de)越(yue)來(lai)越(yue)多,其實(shi)在2015年(nian)消防(fang)(fang)局發布的(de)《關于積極推(tui)動發揮獨立式感(gan)煙火(huo)災探測報(bao)警(jing)器火(huo)災防(fang)(fang)控作(zuo)用(yong)的(de)指導意見》中就鼓勵在其他(ta)居民住宅(zhai)內安(an)裝使用(yong)獨立感(gan)煙報(bao)警(jing)器。那么消防(fang)(fang)報(bao)警(jing)器怎么安(an)裝呢?
1、請專業的人員安裝(zhuang)或簡單的報警器也可以自己(ji)動手安裝(zhuang)。
2、如果你購買的是電池款,動手能(neng)力也不強(qiang),也可以考慮買強(qiang)力的雙面膠直接貼到天花(hua)板上(shang),不過要多注意(yi)防(fang)止火(huo)災報警器掉(diao)下(xia)來(lai)。