槽式電纜橋架的選(xuan)擇(ze) 槽式電纜橋架知識
定義
槽式電(dian)(dian)(dian)(dian)纜(lan)(lan)橋架(jia)是一種(zhong)全封閉型電(dian)(dian)(dian)(dian)纜(lan)(lan)橋架(jia),它最適(shi)用于敷(fu)設計(ji)算機電(dian)(dian)(dian)(dian)纜(lan)(lan)、通信(xin)電(dian)(dian)(dian)(dian)纜(lan)(lan)、熱電(dian)(dian)(dian)(dian)偶電(dian)(dian)(dian)(dian)纜(lan)(lan)及其它高靈敏系統的控(kong)(kong)制(zhi)電(dian)(dian)(dian)(dian)纜(lan)(lan)等,它對控(kong)(kong)制(zhi)電(dian)(dian)(dian)(dian)纜(lan)(lan)屏蔽干擾和重腐蝕(shi)環境中電(dian)(dian)(dian)(dian)纜(lan)(lan)的防護(hu)都有較好效果(guo)。
品種選擇
1、需屏蔽電(dian)氣干擾的電(dian)纜網路或有(you)防護(hu)外部(如:有(you)腐(fu)蝕液休,易燃粉塵等環境)影響的要求(qiu)時,應選用槽式(shi)復合型(xing)防腐(fu)屏蔽電(dian)纜橋架(帶(dai)蓋)
2、強腐(fu)蝕性環(huan)境(jing)應采用(F)類(lei)復合環(huan)氧樹脂防腐(fu)阻燃(ran)型(xing)電纜橋架。托臂、支架也(ye)要選用同樣材料,提(ti)高橋架及附件的使用壽命,電纜橋架在容易(yi)積灰和其它需遮蓋的環(huan)境(jing)或戶外(wai)場所宜加蓋板。
3、除(chu)上(shang)述情況外,可根(gen)據現(xian)場(chang)(chang)還環境及(ji)技術要求選用托(tuo)盤式(shi)、槽式(shi)、梯級式(shi)、玻璃(li)防(fang)腐阻燃電(dian)纜橋(qiao)架(jia)或鋼(gang)質普(pu)通型橋(qiao)架(jia)。在容(rong)易積灰和其它(ta)需(xu)遮蓋(gai)的環境或戶外場(chang)(chang)所(suo)宜(yi)加蓋(gai)板。
4、在(zai)公共通道或(huo)戶(hu)(hu)外(wai)跨(kua)(kua)越道路段(duan),底層梯級的底部宜加(jia)墊板或(huo)在(zai)該段(duan)使用托盤。大跨(kua)(kua)距跨(kua)(kua)越公共通道時,可(ke)根(gen)據用戶(hu)(hu)要求提高橋架的載荷能(neng)力或(huo)選用行(xing)架。
5、大跨距(>3m)要選用復合型橋架(jia)。
6、戶外(wai)要(yao)選用復合環(huan)氧樹指橋架。
規格選擇
1、橋(qiao)架的(de)寬度和高度就按下表選擇(ze),并應符合電(dian)纜填充率(lv)不超過有關標準規(gui)范的(de)規(gui)定值,動(dong)力電(dian)纜可取(qu)40-50%,控制電(dian)纜可取(qu)50-70%,另外需予留(liu)10-25%的(de)式程發展余(yu)量。
2、各(ge)種(zhong)彎通及附(fu)件規格應符合工程布置條件并與(yu)橋架(jia)相(xiang)配套。
3、支、吊架規(gui)格的(de)選(xuan)擇,應按橋架規(gui)格、層數、跨(kua)距等條件配置(zhi)。并應滿足荷載(zai)的(de)要求。
4、橋架橫截面(mian)積的選擇
配置
1、戶(hu)內支(zhi)、吊短跨距一(yi)般采取1.5-3m。戶(hu)外立柱中跨距一(yi)般采取6m。
2、非(fei)直線段的支(zhi)、吊架配置就遵循以下(xia)原則。當橋架寬度300mm時,除符(fu)合下(xia)述條件外,在非(fei)直線段中部還應增設一個支(zhi)、吊架。
3、橋架多層(ceng)設置時(shi)層(ceng)間中心(xin)距為200,250,300,350mm。
4、橋架直線(xian)段每隔50m應予留伸縮縫20-30mm(金屬(shu)橋架)。