槽式電(dian)纜橋(qiao)(qiao)架的(de)選擇 槽式電(dian)纜橋(qiao)(qiao)架知識
定義
槽式電(dian)(dian)(dian)(dian)纜(lan)橋(qiao)架(jia)是一種全(quan)封(feng)閉型(xing)電(dian)(dian)(dian)(dian)纜(lan)橋(qiao)架(jia),它(ta)最適用于敷設(she)計算(suan)機電(dian)(dian)(dian)(dian)纜(lan)、通信(xin)電(dian)(dian)(dian)(dian)纜(lan)、熱電(dian)(dian)(dian)(dian)偶電(dian)(dian)(dian)(dian)纜(lan)及其它(ta)高靈(ling)敏系(xi)統(tong)的控制(zhi)電(dian)(dian)(dian)(dian)纜(lan)等(deng),它(ta)對控制(zhi)電(dian)(dian)(dian)(dian)纜(lan)屏蔽(bi)干擾和重腐蝕環境中電(dian)(dian)(dian)(dian)纜(lan)的防護都(dou)有(you)較好效果(guo)。
品種選擇
1、需屏蔽電氣干(gan)擾的電纜網路或有防護外(wai)部(如:有腐(fu)蝕(shi)液休(xiu),易燃粉塵(chen)等(deng)環境)影響的要求(qiu)時(shi),應選用槽式復合(he)型防腐(fu)屏蔽電纜橋架(帶蓋)
2、強腐蝕性(xing)環境應采用(F)類復合環氧樹脂防腐阻(zu)燃型電(dian)纜橋(qiao)架(jia)(jia)。托臂、支架(jia)(jia)也要(yao)選用同樣材料,提高橋(qiao)架(jia)(jia)及(ji)附件的使用壽(shou)命,電(dian)纜橋(qiao)架(jia)(jia)在容(rong)易(yi)積灰(hui)和(he)其(qi)它(ta)需(xu)遮蓋的環境或戶外場所宜加(jia)蓋板。
3、除上(shang)述(shu)情(qing)況外,可根據現場還(huan)環境及技術要求選用托(tuo)盤式(shi)、槽(cao)式(shi)、梯級式(shi)、玻(bo)璃防腐阻燃電纜橋架(jia)或(huo)鋼質普通(tong)型橋架(jia)。在(zai)容易積灰和其它需遮蓋的(de)環境或(huo)戶(hu)外場所(suo)宜(yi)加(jia)蓋板。
4、在公(gong)共通(tong)道或戶外(wai)跨(kua)越道路段,底層(ceng)梯級(ji)的(de)底部宜加墊板(ban)或在該段使用托盤。大跨(kua)距跨(kua)越公(gong)共通(tong)道時,可根據用戶要求提高(gao)橋(qiao)架的(de)載荷能力或選用行架。
5、大(da)跨距(>3m)要選用復合型橋架。
6、戶外要選(xuan)用復合環(huan)氧(yang)樹指橋架。
規格選擇
1、橋架的寬度(du)和高度(du)就按下表選擇,并應符合電(dian)(dian)纜(lan)填充率不(bu)超過(guo)有關標準規范的規定(ding)值,動力電(dian)(dian)纜(lan)可(ke)取40-50%,控制電(dian)(dian)纜(lan)可(ke)取50-70%,另外需予留10-25%的式程(cheng)發展余量。
2、各種彎(wan)通及附件規格應符合(he)工程布(bu)置(zhi)條件并與橋架(jia)相配套(tao)。
3、支、吊架規格的選擇,應(ying)按橋架規格、層數、跨(kua)距(ju)等條件(jian)配(pei)置。并(bing)應(ying)滿足荷載的要求。
4、橋(qiao)架橫截面積(ji)的選(xuan)擇(ze)
配置
1、戶內支(zhi)、吊短跨距一(yi)般采取(qu)(qu)1.5-3m。戶外立柱中跨距一(yi)般采取(qu)(qu)6m。
2、非直線段的支(zhi)、吊架(jia)配(pei)置就(jiu)遵(zun)循以下原則。當橋架(jia)寬度(du)300mm時,除符合下述(shu)條(tiao)件外,在非直線段中(zhong)部還應(ying)增設一(yi)個支(zhi)、吊架(jia)。
3、橋架多(duo)層設置時層間中心距為200,250,300,350mm。
4、橋架(jia)直線段(duan)每隔50m應予(yu)留伸縮縫20-30mm(金屬橋架(jia))。