一、消防滅火系統有哪幾種
消(xiao)(xiao)防滅(mie)(mie)火系(xi)統類型(xing)一般分為:火災(zai)自(zi)動報警系(xi)統、氣體滅(mie)(mie)火系(xi)統、泡沫滅(mie)(mie)火系(xi)統、防排煙(yan)系(xi)統、消(xiao)(xiao)防栓系(xi)統、滅(mie)(mie)火器配置、自(zi)動噴(pen)水滅(mie)(mie)火系(xi)統、火災(zai)應急照明(ming)和(he)疏散指示標志。
這些消防滅火系統一般都用在住宅、配電室、樓梯間、走道、地下車(che)庫等建筑(zhu)物(wu),幾乎所(suo)有建筑(zhu)物(wu)都要安裝。
二、消防滅火系統工作原理是什么
1、自動報警系統的工作原理
火(huo)(huo)災(zai)(zai)自動報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)系(xi)統應(ying)由觸發(fa)裝(zhuang)(zhuang)置、災(zai)(zai)報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)裝(zhuang)(zhuang)置、災(zai)(zai)警(jing)(jing)(jing)(jing)報(bao)(bao)(bao)裝(zhuang)(zhuang)置和(he)電源(yuan)等四部分組成,火(huo)(huo)災(zai)(zai)報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)大致過程:當煙、溫度(du)、光、氣體濃(nong)度(du)等火(huo)(huo)場參(can)數超過某一給定閾值時(shi),火(huo)(huo)災(zai)(zai)探測(ce)器動作(zuo),發(fa)出(chu)報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)號,該(gai)信號經過連接導線傳送至區域火(huo)(huo)災(zai)(zai)報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)控(kong)制器和(he)(或)集中火(huo)(huo)災(zai)(zai)報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)控(kong)制器,發(fa)出(chu)聲、光報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)信號,同時(shi)顯(xian)示火(huo)(huo)災(zai)(zai)發(fa)生的部位,以通知消防值班(ban)人員(yuan)做(zuo)出(chu)反應(ying),這也就(jiu)是我們(men)通常所說的火(huo)(huo)災(zai)(zai)自動報(bao)(bao)(bao)警(jing)(jing)(jing)(jing)系(xi)統的工作(zuo)原理(li)。
2、防排煙系統的工作原理
當(dang)(dang)發(fa)生災后,操作機(ji)構在煙感報(bao)警(jing)電信號(hao)(hao)作用下,將(jiang)風閥(fa)自動打開,并啟動送風機(ji)與排煙風機(ji),當(dang)(dang)排煙管(guan)內(nei)的(de)氣流達到280°C時,管(guan)道防火(huo)閥(fa)熔斷器熔斷。關(guan)(guan)閉防火(huo)閥(fa),關(guan)(guan)閉信號(hao)(hao)通過(guo)輸入模(mo)塊(kuai)發(fa)送至控制(zhi)器,自動或手動啟動相應(ying)控制(zhi)模(mo)塊(kuai)去關(guan)(guan)閉排煙機(ji)。
在有(you)空調設備時(shi),空調送(song)風管道內的氣流(liu)溫度達到70°C時(shi),防(fang)火熔斷器動(dong)作,關(guan)(guan)閉(bi)防(fang)火閥,關(guan)(guan)閉(bi)信(xin)號(hao)通(tong)過輸入(ru)模塊(kuai)(kuai)傳送(song)至控(kong)制(zhi)器,控(kong)制(zhi)器則(ze)根據聯(lian)動(dong)關(guan)(guan)系給控(kong)制(zhi)模塊(kuai)(kuai)信(xin)號(hao),關(guan)(guan)閉(bi)空調機。
3、泡沫系統的工作原理
(1)閉式泡沫噴淋滅火系統工作原理
當有(you)火災發生時,閉式噴頭的(de)(de)玻璃球破裂噴水,水流(liu)指示器、濕(shi)式報(bao)警閥動作,有(you)信號(hao)傳(chuan)至控(kong)制柜(ju),此時,手動或自動開啟消防泵(beng)比例(li)(li)混(hun)合裝(zhuang)置(zhi)上的(de)(de)電磁閥及管路閥門,系統工作。一(yi)定壓力的(de)(de)消防水經泡(pao)(pao)沫(mo)(mo)比例(li)(li)混(hun)合裝(zhuang)置(zhi)與泡(pao)(pao)沫(mo)(mo)液混(hun)合,形成(cheng)一(yi)定比例(li)(li)的(de)(de)泡(pao)(pao)沫(mo)(mo)混(hun)合液,經噴頭生成(cheng)空氣泡(pao)(pao)沫(mo)(mo)滅(mie)火。
系統組(zu)成:閉式泡(pao)沫噴(pen)淋(lin)滅(mie)火系統主要由消防(fang)水泵泡(pao)沫比例混合裝置(zhi)、閉式噴(pen)頭、水流(liu)指(zhi)示器、濕(shi)式報警閥及其它閥門、管道等組(zu)成。
(2)開式泡沫噴淋滅火系統的工作原理
當有火(huo)災(zai)發(fa)生(sheng)時,安(an)裝于保護區的火(huo)災(zai)探測器(qi)有信號傳(chuan)至控制(zhi)柜,此(ci)時,手動或自動開啟雨淋閥(fa)、消(xiao)防(fang)(fang)泵比例混(hun)(hun)合器(qi)上的電磁閥(fa)及管路(lu)閥(fa)門,系統(tong)工(gong)作(zuo)。壓力消(xiao)防(fang)(fang)水經泡沫(mo)比例混(hun)(hun)合裝置與泡沫(mo)液(ye)混(hun)(hun)合,形成一定(ding)比例的泡沫(mo)混(hun)(hun)合液(ye),經噴頭生(sheng)成空氣泡沫(mo)滅火(huo)。
系(xi)統組成:開式泡(pao)沫噴淋滅火系(xi)統主(zhu)要由消防水泵、泡(pao)沫比例混合裝(zhuang)置、開式噴頭(tou)、雨(yu)淋閥(fa)及其它閥(fa)門、管道等(deng)組成。
4、室內外消火栓系統的工作原理
消(xiao)(xiao)火栓開啟,有水(shui)噴(pen)出(chu),恒壓泵(beng)啟動,恒壓對(dui)管網補壓,按(an)(an)(an)下破玻按(an)(an)(an)鈕,消(xiao)(xiao)防(fang)中心(xin)收到破玻按(an)(an)(an)鈕報警(jing)信號,警(jing)鈴鳴(ming)響,直接啟動主消(xiao)(xiao)防(fang)水(shui)泵(beng),消(xiao)(xiao)防(fang)水(shui)泵(beng)對(dui)管網進行加壓,消(xiao)(xiao)火栓上的啟泵(beng)指示燈亮。消(xiao)(xiao)防(fang)中心(xin)收到消(xiao)(xiao)防(fang)水(shui)泵(beng)運(yun)行信號。
因水(shui)泵(beng)壞或水(shui)池無水(shui)時,消(xiao)防(fang)車對水(shui)泵(beng)接合器進行加(jia)壓,保(bao)證消(xiao)防(fang)系統(tong)能正(zheng)常運行。(水(shui)泵(beng)能手動(dong)(dong)啟(qi)動(dong)(dong),消(xiao)防(fang)中心手動(dong)(dong)啟(qi)動(dong)(dong)、自動(dong)(dong)啟(qi)動(dong)(dong))。
5、噴淋自動滅火系統的工作原理
噴(pen)淋頭達到(dao)額(e)定溫度時,玻璃(li)內的液體(ti)發熱膨脹,玻璃(li)管(guan)破碎,噴(pen)淋頭噴(pen)水(shui)(shui)(shui),水(shui)(shui)(shui)流指示器報(bao)(bao)警(jing)(jing)(jing),消(xiao)防中(zhong)(zhong)(zhong)心(xin)收到(dao)報(bao)(bao)警(jing)(jing)(jing)信號,力(li)下降,水(shui)(shui)(shui)池或恒壓(ya)(ya)泵補壓(ya)(ya),濕(shi)式報(bao)(bao)警(jing)(jing)(jing)閥(fa)動(dong)作,水(shui)(shui)(shui)力(li)警(jing)(jing)(jing)鐘鳴響,壓(ya)(ya)力(li)開(kai)關報(bao)(bao)警(jing)(jing)(jing),消(xiao)防中(zhong)(zhong)(zhong)心(xin)收報(bao)(bao)警(jing)(jing)(jing)信號,水(shui)(shui)(shui)泵起泵加壓(ya)(ya)。消(xiao)防中(zhong)(zhong)(zhong)心(xin)收到(dao)噴(pen)淋泵運行信號。因水(shui)(shui)(shui)泵壞或水(shui)(shui)(shui)池無水(shui)(shui)(shui)時,消(xiao)防車對(dui)水(shui)(shui)(shui)泵接合器進行加壓(ya)(ya),保(bao)證消(xiao)防系統(tong)能(neng)正常(chang)運行。(水(shui)(shui)(shui)泵能(neng)手動(dong)啟(qi)動(dong),消(xiao)防中(zhong)(zhong)(zhong)心(xin)手動(dong)啟(qi)動(dong)、自動(dong)啟(qi)動(dong))。
6、氣體自動滅火系統的工作原理
感(gan)煙或(huo)(huo)感(gan)溫探(tan)測器任一報(bao)警(jing),主機(ji)(ji)(ji)(ji)收到(dao)信號,警(jing)鐘(zhong)鳴(ming)響,感(gan)煙與感(gan)溫探(tan)測器同(tong)時報(bao)警(jing),主機(ji)(ji)(ji)(ji)收到(dao)信號,警(jing)鐘(zhong)鳴(ming)響,光(guang)報(bao)警(jing)器鳴(ming)響。30S后聯(lian)動(dong)風閥、停(ting)空(kong)(kong)調(diao)新(xin)風機(ji)(ji)(ji)(ji)等、啟(qi)動(dong)氣體進(jin)行滅火(huo)(huo)(因誤報(bao)時在30S內按(an)(an)下門口或(huo)(huo)主機(ji)(ji)(ji)(ji)上(shang)的急(ji)停(ting)按(an)(an)鈕(niu)停(ting)止放氣)。人(ren)員發現(xian)火(huo)(huo)災時,直接(jie)按(an)(an)下門口或(huo)(huo)主機(ji)(ji)(ji)(ji)上(shang)的緊急(ji)放氣按(an)(an)鈕(niu),直接(jie)聯(lian)動(dong)風閥、停(ting)空(kong)(kong)調(diao)新(xin)風機(ji)(ji)(ji)(ji)等啟(qi)動(dong)氣體進(jin)行滅火(huo)(huo)。
因主機不能正常啟動(dong)氣(qi)體(ti)滅(mie)火(huo)時,直按(an)用機械啟動(dong)氣(qi)體(ti)進行(xing)滅(mie)火(huo)。
7、防火卷簾的工作原理
在(zai)火(huo)(huo)災(zai)發(fa)生時起(qi)(qi)防火(huo)(huo)分區隔(ge)斷作用,在(zai)火(huo)(huo)災(zai)發(fa)生時,感(gan)煙探(tan)測器(qi)報警(jing),災(zai)信號送到卷(juan)(juan)簾(lian)門制(zhi)柜(ju),控制(zhi)柜(ju)發(fa)出啟(qi)動(dong)信號,卷(juan)(juan)簾(lian)門自動(dong)降(jiang)到距(ju)地(di)1。8米的(de)(de)位置(特殊部位的(de)(de)卷(juan)(juan)簾(lian)門也可(ke)(ke)一(yi)步(bu)到底(di)),如果感(gan)溫(wen)探(tan)測器(qi)再(zai)報警(jing),卷(juan)(juan)簾(lian)門才降(jiang)到底(di)。報警(jing)狀態時,人(ren)員可(ke)(ke)手動(dong)按(an)住上(shang)行(xing)按(an)鈕升起(qi)(qi)卷(juan)(juan)簾(lian),人(ren)過去后放開按(an)鈕后防火(huo)(huo)門又自動(dong)下行(xing)。
8、消防廣播的工作原理
當火災發生(sheng)時(shi),災區域/層(ceng)(如n層(ceng))的消防(fang)煙感(gan)溫感(gan)等探測器發出(chu)報警動(dong)作信(xin)號,消防(fang)接(jie)收控制(zhi)盤、邏輯控制(zhi)等消防(fang)聯動(dong)裝置自動(dong)(或(huo)手動(dong))啟動(dong),通過消防(fang)發送(song)控制(zhi)盤發出(chu)驅動(dong)和切換控制(zhi)信(xin)號。
一路去啟動消防廣播(bo)錄(lu)放(fang)盤,該盤可選擇播(bo)音(yin)(yin)卡播(bo)音(yin)(yin)或話筒播(bo)音(yin)(yin)作為緊急廣播(bo),并可自(zi)動錄(lu)音(yin)(yin)。
9、恒壓泵的工作原理
當(dang)管網(wang)(wang)泄(xie)漏、系(xi)統(tong)壓(ya)(ya)(ya)力(li)(li)(li)降至設(she)定(ding)壓(ya)(ya)(ya)力(li)(li)(li)下限(xian)時(shi),穩壓(ya)(ya)(ya)水(shui)泵自動啟動,對管網(wang)(wang)進(jin)行補(bu)壓(ya)(ya)(ya),以供消防供水(shui)系(xi)統(tong)保證最(zui)不利點的消防所需壓(ya)(ya)(ya)力(li)(li)(li),當(dang)系(xi)統(tong)壓(ya)(ya)(ya)力(li)(li)(li)達到(dao)設(she)定(ding)壓(ya)(ya)(ya)力(li)(li)(li)上(shang)限(xian)時(shi)穩泵停止(zhi)工作,每次壓(ya)(ya)(ya)力(li)(li)(li)下降時(shi),都重復上(shang)述遠(yuan)行過(guo)程,以穩定(ding)消防管網(wang)(wang)的壓(ya)(ya)(ya)力(li)(li)(li)。
消(xiao)(xiao)防(fang)用水(shui)時,穩(wen)壓(ya)(ya)(ya)泵(beng)(beng)持(chi)續運(yun)行(xing)阻懷壓(ya)(ya)(ya)力(li)(li)的下降(jiang),當力(li)(li)降(jiang)到消(xiao)(xiao)防(fang)主(zhu)泵(beng)(beng)啟(qi)動壓(ya)(ya)(ya)力(li)(li)時,電控系(xi)統(tong)發出報警(jing)信號,啟(qi)動消(xiao)(xiao)防(fang)主(zhu)泵(beng)(beng)進行(xing)供(gong)水(shui),當消(xiao)(xiao)防(fang)主(zhu)泵(beng)(beng)運(yun)行(xing)到達額定流量(liang)種壓(ya)(ya)(ya)力(li)(li)時,控制系(xi)統(tong)關閉主(zhu)泵(beng)(beng)穩(wen)壓(ya)(ya)(ya)水(shui)運(yun)行(xing),當單臺消(xiao)(xiao)防(fang)泵(beng)(beng)運(yun)行(xing)機制信用證(zheng)阻止不住壓(ya)(ya)(ya)力(li)(li)下降(jiang),系(xi)統(tong)壓(ya)(ya)(ya)力(li)(li)降(jiang)至消(xiao)(xiao)防(fang)最低壓(ya)(ya)(ya)力(li)(li)時,消(xiao)(xiao)防(fang)備用泵(beng)(beng)啟(qi)動(有兩(liang)主(zhu)一備時)。